Installation and operation manual
17
EUWA(*)5~24KBZW1
Packaged air-cooled water chillers
4PW61653-1 – 07.2010
General information about the Modbus protocol
The Modicon Modbus protocol implemented in the address card
complies with the content of the following document:
Modicon Modbus Protocol
Reference Guide
June 1996, PI-MBUS-300 Rev. J
The Modbus protocol implemented is of the RTU (Remote Terminal
Unit) type based on character tranmission times. The configuration
uses the multi-drop feature of RS485. The address sent within the
Modbus packet addresses the chiller unit.
Implemented RS485 communication settings for the Modbus
protocol
The RS485 communication settings are implemented as follows:
Baud-rate: 9600
Stop bit: 2
Parity: none
Implemented commands for the Modbus protocol
The implemented commands in the program are as listed:
Note that:
Due to the variety of chillers with installed address cards, no
distinction is made between input variables (with read-only
status) and output variables (with read/write status) so that the
knowledge of the database and its management depends on the
part present on the supervisory system.
Due to the general nature of the system, the address card
answers in the same way to various Modbus commands.
Data representation of the Modbus protocol
Digital
All digital data is coded by a single bit:
"0" for OFF
"1" for ON.
All digital variables are assigned to bits of consecutive registers,
each one having:
the lower-address variable assigned to the less significant bit
the higher-address variable assigned to the most significant
bit.
Analogue and integer data
An analogue and integer value is represented by a 16-bit WORD
register in binary notation. For each register, the first byte
contains the high order bits and the second byte contains the
low order bits.
The analogue variables are represented in tenths:
for example, the value 10.0 is transmitted as 0064h=100d
for example, the value –10.0 is transmitted as FF9Ch=–100d
The integer variables are transferred using the effective
value:
for example, the value 100 is transmitted as 0064h=100d
The address card operates on registers where one register must
be considered at 16-bit.
In case the BMS or supervisory system tries to write a value of a
parameter that is out of range, the writing will be ignored.
Implemented error code
Defining the BMS setting
Activating the Modbus protocol
The Modbus protocol is activated by setting the h23 parameter to 1.
This is a user parameter, refer to "How to consult and modify the user
parameters" on page 15.
Defining the unit’s serial address
To define each unit’s unique serial address required for
communication with the supervisionary system, set parameter h10.
This is a user parameter, refer to "How to consult and modify the user
parameters" on page 15.
Modbus command Meaning Notes
01 read coil status Read digital
variable(s)
obtains current status (ON/
OFF) of a group of logic coils
or discrete input
02 read input
status
Read digital
variable(s)
obtains current status (ON/
OFF) of a group of logic coils
or discrete input
03 read holding
registers
Read analogue
variable(s)
obtains current binary value
in one or more holding
registers
04 read input
registers
Read analogue
variable(s)
obtains current binary value
in one or more holding
registers
05 force single coil Write individual
digital variable(s)
forces single coil to ON or
OFF status
06 preset single
register
Write individual
analogue variable(s)
places a specific binary
value into a holding register
15 force multiple
coils
Write series of
digital variables
forces a series of
consecutive logic coils to be
defined to ON or OFF status
16 preset multiple
registers
Write series of
analogue variables
places specific binary values
into a series of consecutive
holding registers
Code Modbus interpretation Condition
1 Illegal function Message is not supported or the
number of variables required is greater
than the allowed limit (length 20)
4PW61653-1_digital_EN.book Page 17 Thursday, August 26, 2010 1:49 PM
20

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Daikin EUWA water chillers wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info