5.9.2.2 - fan mode
Enter
Select the mode
fan mode
fan mode
2
5.9.2.3 - T°C. MINI Minimum temperature
The electrical back-up can be activated at the same time as the
heat pump to prevent the water temperature from going below
a minimum comfort level of 38oC. The electrical back-up will start
up and raise the water temperature to 43oC, and then it will switch
o and the heat pump will complete the heating cycle.
• Press to return to the main menu.
This function is deactivated by default.
5.9.2.4 - Load shedding -Level authorised
during peak hours
5.9.2.5 - max time Max heating time
Enter
Select mode
T°C. MINI
no
T°C. MINI
yes
Enter
Select the mode
shedding
1
shedding
0
When load shedding is activated you can choose to prevent
certain elements from running (Electrical resistance and
compressor).
• Press to return to the main menu.
If load shedding is switched on:
Mode 0 = No element is allowed to operate
Mode 1 = Only the heat pump is allowed to operate
Mode 2 = The heat pump and back-up are allowed to operate
(neutralising the «peak hours» function)
If the PV function is activated, load shedding cannot be done
through the peak/o-peak hours dry contact. In this case the
timer must be programmed (see § «Programming»).
It is possible to select the length of the desired heating time. The
heat pump water heater can automatically use the electrical back-
up at the same time as the heat pump to speed up the heating
time of the tank.
If you choose MAX time = AUTO, the heating time is limited to a
maximum of 5h during o-peak hours.
• In case of load shedding the «T°C mini» function is not activated.
Factory setting= 1
Mode 1 = Standard mode, automatic ventilation
Mode 2 = Forced ventilation, max speed
Mode 3* = Ventilation activated during water heating periods
and ventilation regulated by an external control
(such as a moisture sensor)
The external control should be connected to connector 2 on the
electronics board in the heat pump water heater. (See appendix
for electrical diagram)
*If PV mode is activated, controlled ventilation (fan moDE 3) is not
available.
• Press to return to the main menu.
Enter
Select time period
between 1 and 24 hours
max time
no
max time
3h
This function is deactivated by default.
• Press to return to the main menu.
5.9.3 -Locking the keyboard
Enter
Select locking level
locking
locking
no
Permanent and automatic locking
The «locking» menu enables you to create three possible levels of
locking for accessing the menus.
In the «Installer» menu turn the dial to «locking.».
NO = Locking is not activated, but manual
locking is possible by pressing
for 3 seconds.
• If a cycle is interrupted by a period where the back-up is not
allowed to run (electricity provider signal or programmed time
slots) it will relaunch during the next authorised period.
•No anti-legionellosis cycle except when returning from holidays
and after a frost protection period of more than 3 days.
•During the anti-legionellosis cycle the temperature is raised
between 55°C and 70°C.
- INSTALLER HEAT PUMP WATER HEATER 200 -270L AIR D/2 - MANUAL-
14
14

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex Edel 200 AIR D-2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Dimplex Edel 200 AIR D-2

Dimplex Edel 200 AIR D-2 Bedienungsanleitung - Holländisch - 48 seiten

Dimplex Edel 200 AIR D-2 Installationsanweisung - Holländisch - 48 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info