520386
21
Zoom out
Zoom in
Vorherige Seite
1/48
Nächste Seite
www.dimplex.de 452163.66.23 · FD 9801 EN-7
LA 60TU English
6.3 Electrical connection
A standard five-core cable is used for connecting the heat pump
to the power supply.
The cable must be provided by the customer. The conductor
cross section is selected in accordance with the power consump-
tion of the heat pump (see appendix Device information) and the
applicable VDE (EN) and VNB regulations.
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility blocking contactor or power contactor) as well
as a 3-pole circuit breaker with common tripping for all external
conductors must be installed in the power supply (tripping current
in compliance with the device information).
The relevant components in the heat pump contain an internal
overload protection.
When connecting, ensure that the incoming supply has a clock-
wise rotating field.
Phase sequence: L1, L2, L3.
ATTENTION!
!!
Ensure that there is a clockwise rotating field: With incorrect wiring the
starting of the heat pump is prevented. A corresponding warning is
indicated on the display of the heat pump manager (adjust wiring).
The control voltage is supplied via the heat pump manager.
The heat pump manager has a 230 V AC-50 Hz power supply
and is connected in compliance with its own operating instruc-
tions.
ATTENTION!
!!
The control cable is essential for the operation of air-to-water heat pumps
for outdoor installation. The control cable and mains cable are to be
routed separately. It is not permissible for the customer to extend the
control cable.
Three separate lines are used as control lines. (These are not in-
cluded in the scope of supply of the heat pump). Two of these ca-
bles are equipped with rectangular plug connectors which must
be connected to the heat pump manager and to the underside of
the switch box. One of these two cables is for the 230 V voltage
level, the other for the extra-low voltage level. The third cable
serves as a communication connection between the heat pump
manager and the electronic expansion valve (N23), and must be
connected to the "field card" on the heat pump manager and to
the expansion valve driver (N23/Network) in the switch box of the
heat pump.
The control lines (not included in the scope of supply) have rec-
tangular plug connectors on both ends. One end is connected to
the heat pump manager, and the other end is connected to the
switch box in the heat pump. The plug connections to the heat
pump are located on the bottom of the switch box.
Two separate lines are used as control lines. One of the lines is
designed for the 230 V control voltage level, the other for the sig-
nal and/or extra-low voltage level.
More detailed information can be found in the operating instruc-
tions of the heat pump manager.
For detailed information, see circuit diagrams in the appendix.
7 Start-up
7.1 General
To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. These measures can also include an additional
warranty under certain conditions (see Warranty).
7.2 Preparation
The following items need to be checked prior to start-up:
All of the heat pump connections must be installed as de-
scribed in chapter 6.
All valves that could impair the proper flow of the heating
water in the heating circuit must be open.
The air intake and air outlet paths must be clear.
The fan must turn in the direction indicated by the arrow.
The settings of the heat pump manager must be adapted to
the heating system in accordance with the manager’s oper-
ating instructions.
Ensure the condensate outflow functions properly.
7.3 Procedure
The heat pump is started up via the heat pump manager. Adjust-
ments should be made in compliance with the instructions.
At hot water temperatures under 7 °C, start-up is not possible.
The water in the buffer tank must be heated to a minimum of
18 °C with the second heat generator.
To ensure a problem-free start-up, the following procedure is to
be implemented:
1) Close all consumer circuits.
2) Ensure that the heat pump has the correct water flow.
3) Use the manager to select the automatic operating mode.
4) In the special functions menu, start the "Start-up" program.
5) Wait until a return temperature of at least 25 °C has been
reached.
6) Now slowly reopen the heating circuit valves in succession
so that the heating water flow is constantly raised by slightly
opening the respective heating circuit. The heating water
temperature in the buffer tank must not be allowed to drop
below 20 °C during this process. This ensures that the heat
pump can be defrosted at any time.
7) When all heat circuits are fully open and a return tempera-
ture of at least 18 °C is maintained, the heat pump start-up
is complete.
ATTENTION!
!!
Operating the heat pump at low system temperatures may cause the heat
pump to break down completely.
21

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex LA 60TU wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Dimplex LA 60TU

Dimplex LA 60TU Bedienungsanleitung und Installationsanweisung - Holländisch - 28 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info