520386
22
Zoom out
Zoom in
Vorherige Seite
1/48
Nächste Seite
EN-8 452163.66.23 · FD 9801 www.dimplex.de
English LA 60TU
8 Cleaning / maintenance
8.1 Maintenance
To protect the paintwork, avoid leaning anything against the de-
vice or putting objects on the device. External heat pump parts
can be wiped with a damp cloth and domestic cleaner.
NOTE
º
Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.
To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
cannot be contaminated. In the event that operating malfunctions
due to contamination still occur, the system should be cleaned as
described below.
8.2 Cleaning the heating system
ATTENTION!
!
!
The integrated dirt trap must be cleaned at regular intervals.
The maintenance intervals should be defined according to the
degree of soiling in the system. The filter insert should also be
cleaned.
For cleaning, the heating circuit must be made pressureless in
the vicinity of the dirt trap, the filter compartment unscrewed, and
the filter insert removed and cleaned. Assembly carried out in re-
verse order requires attention to correct assembly of the screen
inserts and tightness of the screw joints.
The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. They enter the heating system via the
valves, the circulating pumps and/or plastic pipes. It is therefore
essential - in particular with respect to the entire pipework - that
only diffusion-resistant materials are used.
NOTE
º
We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump. We recommend equipping diffusion-open heating systems
with an electrophysical anti-corrosion system (e.g. ELYSATOR system).
Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in the
performance of the liquefier in the heat pump, the system must
be cleaned by a heating technician.
Based on current knowledge, we recommend carrying out the
cleaning with a 5 % phosphor acid or, if more frequent cleaning
is required, with a 5 % formic acid.
In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return of the liquefier of the heat pump.
It is then important that the system be thoroughly flushed using
appropriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the system.
Acids must be used with care and the regulations of the employ-
ers’ liability insurance associations must be adhered to.
The manufacturer's instructions regarding cleaning agent must
be complied with at all times.
8.3 Cleaning the air system
The evaporator, ventilator and condensate outflow should be
cleaned of contamination (leaves, twigs, etc.) before each new
heating period.
ATTENTION!
!
!
Before opening the device, ensure that all circuits are powered down.
To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects when cleaning.
Under extreme weather conditions (e.g. snow drifts), ice may
form on the air intake and air outlet grids. If this happens, the ice
must be removed in the vicinity of the air intake and air outlet
grids to ensure that the minimum air flow is maintained.
To ensure proper drainage from the condensate tray, it must be
regularly inspected and cleaned, if necessary.
All panelling can be removed to allow accessing the inside of the
device.
The two sash fasteners must be opened for this purpose. The
cover must then be slightly tilted forward and lifted off toward the
top.
The upper panels are hooked into the cover panel. Loosen the
two screws for dismantling and unhook the panels by pulling
them back.
Opening the lower covers Closing the lower covers
Opening the upper cover panels Closing the upper cover panels
2
3
1
1
3
2
1111
3
1
2
3
1
2
1.
3.
3.
1.
2.
2.
1.
1.
2.
1.
22

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex LA 60TU wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Dimplex LA 60TU

Dimplex LA 60TU Bedienungsanleitung und Installationsanweisung - Holländisch - 28 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info