English LAW 9IMR - LAW 14ITR
8 Connecting the pipework
and cables to the outdoor
unit
This chapter describes the refrigerant pipe connections and the
electrical cable connections on the outdoor unit.
8.1 Refrigerant pipes
ATTENTION!
!
!
Work on the system must only be performed by authorised
and qualified after-sales service technicians!
Certain requirements with regard to pipe length and rise must
be complied with when installing refrigerant pipes. Once all re-
quirements have been fulfilled, certain preparations must be
made.
Once these are complete, the connecting pipe from the out-
door unit to the indoor unit can be connected.
8.1.1 Requirements for pipe length
and rise
The standard pipe length is 7.5 m. Up to a length of 15 m, no
additional refrigerant filling is required. For pipe lengths over
15 m, the system must be filled with additional refrigerant in ac-
cordance with the table.
*Example: When installing the 14 kW model at a distance of
50 m, 2100 g refrigerant must be added according to the fol-
lowing calculation: (50-15) x 60 g = 2100 g
NOTE
º
If the indoor unit is mounted 4 or more metres higher than the
outdoor unit, a cooling technology specialist must perform a
separate check to ensure that the devices for conveying the
oil up and down the pipes have been installed correctly in the
hot gas pipe.
NOTE
º
The rated output of the device corresponds to the standard
pipe length and the maximum possible length.
ATTENTION!
!
!
Incorrect filling with refrigerant could lead to faults during
operation.
1) Production operation (see model name label)
2) Installation operation (where possible, attach alongside the
maintenance connections for adding or removing refriger-
ant)
3) Total filling (1, + 2,)
8.1.2 Preparation for pipework
The preparation of the pipework takes place in five steps. One
main cause of refrigerant leaks is incorrect flanging. Flanging
must be carried out carefully and according to the following
steps.
Step 1: Cutting pipes and cables
Use the installation kit for pipework or the pipes purchased
from your local dealer.
Measure the distance between the indoor and outdoor
unit.
Cut the pipes slightly longer than the measured distance.
Step 2: Removing burrs
Remove all burrs from the interface of the pipework.
Hold the pipe end downwards so that no burrs can fall into
the pipe.
Step 3: Inserting screw nuts
Remove the screw nuts on the indoor and outdoor unit.
Insert the screw nuts into the deburred pipe.
No nuts can be inserted into the pipe after flanging.
Model
Pipe size (mm)
(diameter: ) Length A (m) Rise B (m) *additional
refrigerant
(g/m)
Gas Liquid Normal Min. Max. Normal Max.
9 kW 15.88
(5/8")
9.52
(3/8") 7.5 3 50 0 30 30
14 kW 15.88
(5/8")
9.52
(3/8") 7.5 3 50 0 30 60
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Copper pipe
90qTilted Uneven Raw
Pipe
Reamer
Hold facing
downwards
Screw nut
Copper pipe
36

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex LAW 9IMR wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info