798317
30
Zoom out
Zoom in
Vorherige Seite
1/76
Nächste Seite
EN-10 452161.66.22 · FD 9912 www.gdts.one
English LI 20TES - LI 28TES
7.5 Electrical connection
7.5.1 General
All electrical connection work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11, N1-J24 to N1-J26 and terminal strip X3. If, due to a
wiring error, the line voltage is mistakenly connected to these
terminals, the heat pump manager will be destroyed.
7.5.2 Electrical installation
1) The electric supply cable for the output section of the heat
pump (up to 4-core) is fed from the electricity meter of the
heat pump via the utility blocking contactor (if required)
into the heat pump (see heat pump operating instructions
for supply voltage).
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping
for all external conductors must be installed in the power
supply for the heat pump (tripping current and characteris-
tic in compliance with the device information).
When connecting the device, ensure that the incoming
supply has a clockwise rotating field L1; L2; L3.
ATTENTION!
!
!
Ensure that there is a clockwise rotating field: With incorrect
wiring the starting of the heat pump is prevented. A
corresponding warning is indicated on the display of the heat
pump manager (adjust wiring).
For detailed information, refer to the circuit diagrams in the
appendix.
2) The three-core electic supply cable for the heat pump
manager (heating controller N1) is fed into the heat pump.
The correct control voltage must be ensured according to
the type plate. The (L/N/PE~230 V, 50 Hz) supply cable for
the heat pump manager must have a constant voltage. For
this reason, it should be tapped upstream from the utility
blocking contactor or be connected to the household
current, as important protection functions may otherwise
be lost during a utility block.
3) The utility blocking contactor (K22) with 3 main contacts
(1/3/5 // 2/4/6) and an auxiliary contact (NO contact 13/
14) should be dimensioned according to the heat pump
output and must be supplied by the customer.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to connector terminal N1-
J5/ID3. CAUTION! Extra-low voltage!
4) The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the
radiator output and must be supplied by the customer. It is
controlled (230 V AC) by the heat pump manager via
terminals X2/N and N1-J16/NO10.
5) The contactors mentioned above in points 3 and 4 are
installed in the electrical distribution system. Mains cables
for the installed heaters must be laid and secured in
accordance with the valid standards and regulations.
6) All installed electric cables must have permanent wiring.
7) The heat circulating pump (M13) is activated via the con-
tact N1-J13/NO5. The connection points for the pump are
X2/M13 and X2/N. When using pumps where the switch-
ing capacity exceeds the output, a coupling relay must be
interposed.
8) The auxiliary circulating pump (M16) is activated via the
contact N1-J16/NO9. The connection points for the pump
are X2/M16 and X2/N. A coupling relay is already
integrated in this output.
9) The domestic hot water circulating pump (M18) is acti-
vated via the contact N1-J18/NO6. The connection points
for the pump are X2/M18 and X2/N. When using pumps
where the switching capacity exceeds the output, a cou-
pling relay must be interposed.
10) The return sensor (R2) is integrated into air-to-water heat
pumps for indoor installation.
The connection to the HPM is at terminals X3/GND and
N1-J2/U2.
11) The external sensor (R1) is connected to terminals X3/GND
and N1-J2/U1.
12) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/ GND and N1-J2/U3.
7.5.3 Connecting an electronically
regulated circulating pump
Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. A coupling relay is therefore installed or must be in-
stalled between the output of the heat pump manager and the
electronically regulated circulating pump. This is not necessary
if the maximum permissible operating current of the heat pump
manager of 2 A and the maximum permissible starting current
of the heat pump manager of 12 A are not exceeded by the
electronically regulated circulating pump or a relevant approval
has been issued by the pump manufacturer.
ATTENTION!
!
!
It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.
30

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex LI 24TES wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info