798317
31
Zoom out
Zoom in
Vorherige Seite
1/76
Nächste Seite
www.gdts.one 452161.66.22 · FD 9912 EN-11
LI 20TES - LI 28TES English
8Start-UP
8.1 General Information
To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by
the manufacturer. These measures can also include an addi-
tional warranty under certain conditions (see Warranty).
8.2 Preparation
The following items need to be checked prior to start-up:
All of the heat pump connections must be established as
described in Chapter 6.
All valves that could impair the proper flow of the heating
water in the heating circuit must be open.
The air intake and air outlet paths must be clear.
The ventilator must turn in the direction indicated by the
arrow.
The settings of the heat pump manager must be adapted
to the heating system in accordance with the controller’s
operating instructions.
Ensure the condensate outflow functions.
8.3 Procedure
The heat pump is started up via the heat pump manager. Ad-
justments should be made in compliance with the instructions.
At hot water temperatures under 7 °C, start-up is not possible.
The water in the buffer tank must be heated to a minimum of
18 °C with the second heat generator.
To ensure a problem-free start-up, the following procedure is to
be implemented:
1) Close all consumer circuits.
2) Ensure that the heat pump has the correct water flow.
3) Use the manager to select the automatic operating mode.
4) In the special functions menu, start the "Start-up" program.
5) Wait until a return temperature of at least 25 °C has been
reached.
6) Now slowly reopen the heating circuit valves in succession
so that the heating water flow is constantly raised by
slightly opening the respective heating circuit. The heating
water temperature in the buffer tank must not be allowed
to drop below 20 °C during this process. This ensures that
the heat pump can be defrosted at any time.
7) When all heat circuits are fully open and a return tempera-
ture of at least 18 °C is maintained, the heat pump start-up
is complete.
ATTENTION!
!
!
Operating the heat pump at low system temperatures may
cause the heat pump to break down completely.
9 Maintenance / Cleaning
9.1 Maintenance
To protect the paintwork, avoid leaning or putting objects on
the device. External heat pump parts can be wiped with a damp
cloth and domestic cleaner.
NOTE
º
Never use cleaning agents containing sand, soda, acid or
chloride as these can damage the surfaces.
To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating sys-
tem can not be contaminated. We recommend protecting the
evaporator by installing a bird guard in the inlet duct. At least
80% of the cross section of the grating should be open. In the
event that operating malfunctions due to contamination still
occur, the system should be cleaned as described below.
9.2 Cleaning the Heating System
The ingress of oxygen into the heating water circuit may result
in the formation of oxidation products (rust), particularly if steel
components are used. These products enter the heating sys-
tem via the valves, the circulating pumps and/or plastic pipes. It
is therefore essential - in particular with respect to the piping of
underfloor heating systems - that only diffusion-proof materials
are used.
NOTE
º
We recommend the installation of a suitable corrosion
protection system to prevent the formation of deposits (e.g.
rust) in the condenser of the heat pump.
Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in
the performance of the liquifier in the heat pump, the system
must be cleaned by a heating technician.
According to today's state of knowledge, we recommend using
a 5 % phosphoric acid solution for cleaning purposes. However,
if cleaning needs to be performed more frequently, a 5 % for-
mic acid solution should be used.
In either case, the cleaning fluid should be at room tempera-
ture. We recommend flushing the heat exchanger in the direc-
tion opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating
system circuit, we recommend connecting the flushing device
directly to the flow and return flow of the liquifier of the heat
pump.
It is important that the system be thoroughly flushed using ap-
propriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the sys-
tem.
Acids must be used with great care and all relevant regulations
of the employers' liability insurance associations must be ad-
hered to.
The manufacturer's instruc4tions regarding cleaning agent
must be complied with at all times.
31

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex LI 24TES wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info