9.2.1 Motion detector activated for presence verification
Symptom Cause and / or remedy
LED is on during WALK TEST, but no
alarm is triggered
In case of presence verification an alarm is only triggered, if no
motion has been detected over the programmed period ( time-out
can be selected according to section 5.1.2.1)
WALK TEST has been set, but LED is not
on
Power supply of the motion detector is missing (=> check cable,
connector and power supply)
Power supply not on since two minutes (stabilize time of PIR-motion
detector)
Alarming with announcement „emergency
call activated, sensor 1 activated “
Motion detector has been connected after the unit has been switch on!
Alarming with announcement „emergency
call activated, sensor failure “
Motion detector has been disconnected after the unit has been switch
on!
9.3 Sensor-1-contact
Symptom Cause and /or remedy
Sensor-1 does not trigger an alarm Inactive waiting period by switching on the unit or between two alarms
is not expired
Supervision has been temporarily deactivated (deactivation)
Supervision is deactivated at current position of the selection switch
(I/II/III) ( section 5.1)
Motion detection is programmed to verify presence ( section
5.1.2.1), an alarm is only triggered if no motion is detected over a
programmed time.
Test mode => check section 4.2.3
„Alarm due to sensor 1“ is announced, but
the motion detector has been temporarily
deactivated
The power supply of the unit has been cut off for a short period
The function switch has been switched to PROG or OFF after
temporarily deactivation.
9.4 Sensor-2-contact
Symptom Cause and /or remedy
Sensor-2 does not trigger an alarm Inactive waiting period by switching on the unit or between two alarms
is not expired
Supervision has been temporarily deactivated (deactivation)
Supervision is deactivated at current position of the selection switch
(I/II/III) ( section 5.2)
Sensor-2 is activated as an emergency button ( section 5.2.2)
Test mode => check section 4.2.3
„Alarm due to sensor 2“ is announced, but
the motion detector has been temporarily
deactivated
The power supply of the unit has been cut off for a short period
The function switch has been switched to PROG or OFF after
temporarily deactivation.
9.5 Sensor-3-contact
Symptom Cause and /or remedy
Sensor-3 does not trigger an alarm Inactive waiting period by switching on the unit or between two alarms
is not expired
Supervision has been temporarily deactivated (deactivation)
Supervision is deactivated at current position of the selection switch
(I/II/III) ( section 5.3)
Contact is still in alarm position. A new alarm can only be triggered,
after the contact returns to its rest position
Test mode => check section 4.2.3
9.6 Acoustical monitoring
Symptom Cause and /or remedy
noise is not triggering an alarm Factory setting supports monitoring of acoustics only on pos. III of
selection switch. ( programming can be altered, see section 5.4)
The unit has been deactivated by DTMF 7 => LED alternatively 4s
on / 4s off
By switching on the unit or after triggering an alarm, the acoustical
monitoring is not active during the waiting time of 20 seconds (
section 7.3) => LED is lit constantly during the waiting time!
Depending on the position of the selection switch, an alarm is triggered
with a different delay. Every time the noise exceeds the pre set level,
the LED is on. ( section 7.4)
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für EasyAlarm CONTROL wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von EasyAlarm CONTROL

EasyAlarm CONTROL Bedienungsanleitung - Deutsch - 32 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info