H-915 installation manual 11/9 TBT502 01
y= 0 relay
1 ext. siren
2 panic
3 fire
4 arm
5 int. siren
Note: If an output is activated by the [5][xy] command, the output will stay active until you press [
∗
]. Then you are back
in the installer programming level again.
Example: Enter [5] [02] to activate the panic output, enter [
∗
] to switch off this output.
[8] Optional devices programming
- for programming of devices which are connected trough serial line.
See corresponding device manual for more information when you install such a device. Press [#] to return to normal
installer programming.
[9] Events history output. If you press [9] in the installer programming level the H-915 control panel will send
information about events history to the special serial interface (printer) which can be connected to the keypad terminals
as an option (the same function as in the User programming level [∗][5]).
Note
: Press [#] to return to the standby level from the installer programming level when you finish programming. All
programming is stored in the non voltage memory. Additionally, the current working mode is stored in the non voltage
memory. If power is switched completely off, the control panel will return to the original settings when the power comes
on again.
For example, if the power is switched off completely and an alarm condition is present, the control panel will start in the
alarm condition when the power is switch on again.
If there is any reason to switch the power completely off (for example when you want to extend the system with an
optional device), we recommend to enter the installer programming level at first.
FACTORY DEFAULT SETTING:
Master Code: 1234
Installer Code: 1010
No other access codes programmed
Zone definition: 1 delay
2 next delay interior
3 interior instant
4 instant
5 instant
6 instant
Timers: Exit delay: 40 sec.
Entry delay: 20 sec.
Alarm duration: 3 min.
Alarm outputs: Technical Relay only
Fire E.siren, I.siren, Relay, Fire
Intruder E.siren, I.siren, Relay
Panic Panic only
Optional functions: Arming confirmed only by keypad's buzzer
Loop 6 works as zone 6 input
Number of attempts to enter code: 5
Quick arming: disabled
Auto AT HOME arming: disabled
If somebody in: alarm can be adible
COMPLETE RESET:
In the event that the master code or installer code is forgotten (or for some other reason), it is possible to completely
reset all settings of the H-915 to the factory default. To do this, disconnect the power completely (A.C. and back up
battery). Then install the jumper RESET on the control panel board.
Reconnect the power supply. Wait 2 seconds and remove the jumper. The control panel will perform a self test and
end in installer programming mode (press [#] to entr stand by).
WHEN INSTALLATION IS FINISHED:
Explain and demonstrate all the functions of the H-915 system to the users. Be sure that they know how to program the
access codes and how to operate the system.