JA-82K control panel installation manual - 18 - MKH51103
fig. 18 continues
Function Sequence Options
Factory
default
Setting to
comply with
EN-50131-1
Notes
Wireless-siren alarms enabled (IW & EW)
38x
381 = YES 380 = NO
YES
NO = siren disabled
Auto-bypass user approval via the key
If a detector is active during setting (arming), the
system will automatically bypass it (them),
immediately (390), or after keying in (391)
39x
391 = YES 390 = NO
NO YES
to confirm auto-bypass while
exiting Service mode press #
twice
Final-door detectors
If this function is used, then Exit & Entrance delay
settings are multiplied by 30s. A triggered final-door
detector extends the exit delay, de-triggering of the
last final-door detector ends the exit delay.
65x
0 none
1 detectors 01 to 05,
2 detectors 46 to 50
x = 0
If multiple F. door detectors are
used, then triggered state=any of
them, non triggered state=all of
them
Partial setting (arming) or system splitting
66x
0 unsplit system
1 partial setting (A, AB, ABC)
2 split system A, B & common
section C (set if A & B are
set)
0
Automatic Summer Time (Daylight Saving
Time)
680x
6801 = YES 6800 = NO
NO
Changes internal clock + 1h on
Apr.1 & -1h on Nov.1
Pulse reaction of tamper sensors
Tamper alarm in response to an increase in the
number of triggered tamper sensors
681x
6811 = ignore permanently
triggered tamper sensors, i.e.
only react to an increase in the
number of triggered tamper
sensors
6810 = react with a tamper
alarm to all triggered tamper
sensors
x = 0
Suppresses the indication of
permanently triggered tamper
sensors
Operating the PG outputs using 8 and 9
682x
6821 = YES 6820 = NO
YES
if yes then arrow keys can also
operate PGX
Permanent alarm status display for a set
system
683x
6831 = YES 6830 = NO
NO
suppresses the 3min. display
timeout
Tamper alarm if unset (disarmed)
684x
6841 = YES 6840 = NO
NO
YES
Recording PG output activation to memory
685x
6851 = YES 6850 = NO
YES
Engineer reset
686x
6861 = YES 6860 = N0
NO
Social alarm
687x
6871 = YES 6870 = N0
NO
Annual check requirement display
If enabled then 12 months after exiting Service
Mode an annual technical check request is
displayed on the keypad unit (mobile phone &
ARC notification optional)
690x
6901 = YES 6900 = NO
NO
Another time period can be
selected by changing the system
date before exiting service mode
Only single alarm indication
If enabled then another intruder alarm can not
be triggered during an intruder alarm currently
in progress.
691x
6911 = YES 6910 = NO
NO
YES
6911 = no other alarms are
reported during an intruder alarm
Setting (arming) by service code
692x
6921 = YES 6920 = NO
NO
only with the master code
holder’s approval
Audible panic alarm
693x
6931 = YES 6930 = NO
NO
Higher control-panel receiver-sensitivity
Extends the communication range if there is no
RF interference
694x
6940 = normal
6941 = higher
normal
Access by Code plus Card
If enabled and there is a code and card
assigned to the same user, then both of them
must be presented for setting (arming) control
(in any order).
695x
6951 = Code+Card
6950 = Code or Card
code or
card
YES
Audible 24h intruder alarm
696x
6961 = YES 6960 = NO
YES
0= silent 24h intruder alarm
Service mode only with service + user
(master) code
697x
6971 = YES 6970 = NO
NO YES
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

jablotron-ja-82k-oasis

Suche zurücksetzen

  • Rauchmelder schlägt Alarm ohne Rauch, kann das am Akku liegen? Eingereicht am 29-8-2018 09:05

    Antworten Frage melden
  • Wie kann ich einen irrtümlichen Sabotaschealarm im System neutralisieren?
    Danke Hubert Eingereicht am 21-7-2017 17:57

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Jablotron JA-82K OASIS wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Jablotron JA-82K OASIS

Jablotron JA-82K OASIS Installationsanweisung - Deutsch - 23 seiten

Jablotron JA-82K OASIS Bedienungsanleitung - Englisch - 23 seiten

Jablotron JA-82K OASIS Zusatzinformation - Englisch - 1 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info