7.3 Operating characteristics
1. Set temperature in cooling
Range:10~20℃ (default12℃)
If the set temperature is between 10~13, the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
2
If the set temperature is between 14~20℃,the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
2
2. Set temperature in heating
Range:35~50℃ (default40℃)
If the set temperature is between 35~44℃,the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
2
If the set temperature is between 45~50℃,the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
0
5. Fan speed control
For correct operation of the unit with different ambient
temperatures, the microprocessor controls the fan speed based
on the ambient temperature and the condensing or evaporation
temperature as well as compressor frequency, thus enabling heat
exchange to be increased and/or decreased, maintaining the
condensing or evaporation temperature practically constant.
6. Frost prevention protection
To prevent the water freezing and damaging the plate heat
exchanger, the microprocessor will perform antifreeze protection
program if the heat exchanger temperature or the water
temperature below a certain temperature.
a. In the cooling mode or water pump mode: if the heat exchanger
temperature or the outlet temperature sensor is less than 3, the
compressor will shut down and the controller display Pb code, the
water pump will continue to run until the heat exchanger
temperature or the outlet temperature sensor is above 8and the
unit will resume normal operation.
b. In the heating mode or standby mode: if the heat exchanger
temperature or the inlet temperature sensor is less than 8, the
controller display Pb code, the water pump will continue to run until
the heat exchanger temperature or the inlet temperature sensor is
above 15. If the heat exchanger temperature or the inlet
temperature sensor continues to fall below 5, the unit will be
forced heating operation, the compressor and the water pump will
be running until the heat exchanger temperature or the inlet
temperature sensor is above 15.
c. If the ambient temperature is less than 8and the heat
exchanger temperature or the inlet temperature sensor is less
than 2, the electric exchanger temperature heating will turn on
until the heat exchanger temperature or the inlet temperature
sensor is above 7℃.
If the unit is likely to operate below 0, it is advisable to add
antifreeze to the water system to prevent the unit from freezing the
system in the event of a power cut off or failure.
7. Fin heat exchanger high temperature protection
When the fin heat exchanger temperature over than 62°C, system
will shut down, but not returns to normal operation until the
temperature decreased less than 52°C.
8. Comp. discharge temperature protection
If the compressor discharge temperature is more than 115℃,the
compressor will be stop running until the temperature is lower than
83. The compressor starts with a 5-minute delay protection.
The set temperature refers to the set return water temperature or
inlet temperature;
In the event of a temporary power failure, when power returns, the
mode set previously will be retained in the memory.
3. Compressor start up delay
To prevent the compressor frequent start and stop, the compressor
must ensure that each start since the last stop since the minimum
time of 300 seconds.
4. The pump control and the flow switch control
The electronic board includes two pumps control output. The pump 1
running 3 seconds, the pump 2 starts running. The pump 1 starts
when the assembly is powered up and at least 285 seconds before
the compressor starts up and stops 120 seconds after the assembly
shuts down.
After the first 120 seconds of pump1 operation when the water flow
meets the operating requirements, the water flow alarm functions are
activated (differential pressure switch or flow switch). If the differential
pressure switch (or flow switch) detects a continuous closure for 15
seconds, the unit can run normally, otherwise, it will shut down and
display C8 fault.
In the unit operation process, if the continuous 10 seconds to detect
the differential pressure switch (or flow switch) is opened, the unit will
stop running and display C8 fault.
If there is a possibility that the outside temperature may drop
below zero, there is the risk of freezing.
The water circuit MUST BE EMPTIED AND SHUT OFF
POWER (when draining after heat pump operation take care
as the water may be hot) or antifreeze must be added in the
proportion recommended by the manufacturer.
8.
TROUBLE SHOOTING
This section provides useful information for diagnosing and
correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be
carried out by your local technician.
CAUTION
on
off
-1
on
off
-2
off
-2
on
33

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Kaysun KEM-07 DVN1 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Kaysun KEM-07 DVN1

Kaysun KEM-07 DVN1 Bedienungsanleitung - Holländisch - 48 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info