UPS Setting
01:
Output voltage
setting
02:
Programmable
outlets
enable/disable
03:
Programmable outlets
setting
04:
Maximum charger
current setting
05:
LCD display
direction setting
06:
Autonomy
limitation setting
07:
Battery total AH
setting
00:
Exit setting
200/208/220/230/240
110/115/120/127
(Default)
ENA/ DIS
0-999
1/2/4/6/8
RAC: Horizontal
TOE: Vertical
0-999/DIS
7-999
Steps for setting programmable outlet
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Before entering
setting mode, the UPS
should be in Stand-by
mode (off-charging)
and make sure the
battery is connected.
Press and hold the
“Selection” button for
3 seconds to enter
Setting mode
Press the “Up“ button (ON/MUTE) to switch to "02"
of program list. Then press “Enter“ button to enter
value setting of parameter 2. Press the “Up” button
to change the value to “ENA” to enable the
programmable outlet function. Then press “Enter”
button again to confirm the setting.
Press the Upbutton (ON/MUTE) again to
switch to "03" of program list. Then press
“Enter“ button for setting programmable outlet
time. Push “Up” button to change the value of
backup time according your demand. Then
press “Enter” to confirm the setting.
Press “Up“ button
(ON/MUTE) to switch
to "00" of program list.
Then press “Enter”
button to exit setting
menu.
Disconnect AC input
and wait until the LCD
display is off. The new
setting will be
activated when
turning on the UPS
again.
Operating Mode Description
ECO mode
Buck mode when AC is
normal.
Boost mode when AC is normal.
Battery mode
Standby mode
When the input voltage is within voltage
regulated range, UPS will power the output
directly from the mains. ECO is an abbreviation of
Efficiency Corrective Optimizer. In this mode,
when battery is fully charged, the fan will stop
working for energy saving.
When the input voltage is
higher than the voltage
regulation range but
lower than high loss
point, the buck AVR will
be activated.
When the input voltage is lower than the voltage
regulation range but higher than low loss point,
the boost AVR will be activated.
When the input voltage is lower than the
voltage regulation range but higher than low
loss point, the boost AVR will be activated.
When the input voltage is beyond the
acceptable range or power failure and alarm is
sounding every 10 seconds, UPS will backup
power from battery.
UPS is powered off
and no output supply
power, but still can
charge batteries.
MODEL
PM 1500 NetGuard LCD Line
PM 2000 NetGuard LCD Line
PM 3000 NetGuard LCD Line
CAPACITY
1500 VA / 1350 W
2000 VA / 1800 W
3000 VA / 2700 W
INPUT
Acceptable Voltage Range
81-145 VAC or 162-290 VAC
Frequency Range
60/50 Hz (auto sensing)
OUTPUT
Voltage Regulation (AC Mode)
110/115/120/127 VAC or 208/220/230/240 VAC
Voltage Regulation (Batt. Mode)
± 1.5%(before battery alarm)
Frequency Range (Batt. Mode)
50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
Transfer Time
Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode)
Pure Sine Wave
BATTERY
Standard
Model
Battery Type & Number
12 V/7 Ahx4
12 V/9 Ahx4
12 V/9 Ahx6
Charging Voltage
54.8 VDC ± 1%
54.8 VDC ± 1%
82.1 VDC ± 1%
Recharge Time
4 hours recover to 90% capacity
Long-run
Model
Charging Current
N/A
1A/2A/4A/8A
1A/2A/4A/8A
Charging Voltage
54.8 VDC± 1%
82.1 VD ± 1%
PHYSICAL
Standard
Model
Dimension, DXWXH (mm)
510 x 438 x 88
630 x 438 x 88
Net Weight (kg)
19.5
21.5
29.3
Long-run
Model
Dimension, DXWXH (mm)
N/A
410 x 438 x 88
110/115/120/127 VAC: 510 x 438 x 88
208/220/230/240 VAC: 410 x 438 x 88
Net Weight (kg)
11
110/115/120/127 VAC: 13.9
208/220/230/240 VAC: 11.9
ENVIRONMENT
Operating Humidity
0-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 45dB
*Product specifications are subject to change without further notice.
Specifications
WARNING: This is a category C2 UPS product. In a residential
environment, this product may cause radio interference, in which
case the user many be required to take additional measures.
WARNUNG: Dies ist eine USV der Klasse C2. In Wohnansiedlungen
kann dieses Erzeugnis Funkstörungen hervorrufen, dann muss der
Benutzer zusätzliche Maßnahmen ergreifen.
User Manual
PM 1500/2000/3000 NetGuard LCD Line Interactive IEC version: 1. 0
EN
7

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Mustek PowerMust 3000 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info