Installation
29
Climate 5000 MS – 6721830160 (2020/12)
Observe the maximum number of connected indoor units which
depends on the appliance type of the outdoor unit.
Observe maximum piping length and maximum difference in height
between the indoor units and outdoor unit.
Table 7 Piping lengths
Comply with maximum difference in height between the indoor units
and outdoor unit ( Fig. 5).
Observe pipe diameter and further specifications.
Table 8 Alternative pipe diameter
Table 9
3 Installation
3.1 Before installation
CAUTION
Risk of injury from sharp edges!
Wear protective gloves during installation.
CAUTION
Danger of burns!
During operation the pipes become hot.
Make sure, that the pipes cooled down before touching them.
Check the scope of delivery for damage.
Check whether a hissing sound due to negative pressure can be
detected when opening the pipes of the indoor unit.
3.2 Requirements for installation site
Observe minimum clearances (Chapter 2.5 on page 28).
Observe minimum room area.
Table 10 Minimum room area (1 of 3)
Table 11 Minimum room area (2 of 3)
Table 12 Minimum room area (3 of 3)
General notices regarding indoor units
Do not install the indoor unit in a room in which open ignition sources
(for example: open flames, an operating wall mounted gas boiler or
an operating electric heating system) are in operation.
The installation site must not be higher than 2000 m above sea level.
Keep the air inlet and air outlet clear of any obstacles to allow the air
to circulate freely. Otherwise poor performance and higher noise
levels may occur.
Keep TV, radio and and similar appliances at least 1 m away from the
unit and the remote control.
Do not install the indoor unit in rooms with a high humidity
(e.g. bathrooms or utility rooms).
Indoor units with a cooling capacity of 2.0 to 5.3 kW are designed for
a single room.
Notices regarding wall-mounted indoor units
The unit can be installed in a room with a floor area of 4 m2, if the
installation height is at least 1.8 m. If the installation height is lower,
the floor area must be accordingly larger.
Mount the indoor unit on a wall that absorbs vibrations.
Notices regarding ceiling-mounted indoor units
The ceiling construction and suspension system (on site) must be
able to support the weight of the appliance.
Unit type
Climate 5000 MS ...
Maximum overall
pipe length1) [m]
1) Gas side or liquid side
Maximum pipe
length per
connection1) [m]
14 OUE 40 25
18 OUE
21 OUE 60 30
27 OUE
28 OUE 80 35
36 OUE
42 OUE 80 35
Pipe diameter [mm] Alternative pipe diameter [mm]
6.35 (1/4") 6
9.53 (3/8") 10
12.7 (1/2") 12
Specification of the pipes
Min. piping length 3 m
Standard piping length 7.5 m
Additional refrigerant if the pipe length
exceeds 7.5 m (liquid side)
With Ø 6.35 mm (1/4"):
12 g/m
With Ø 9.53 mm (3/8"):
24 g/m
Piping Thickness With Ø 9.53 mm (3/8''):
≥ 0.8 mm.
With Ø 15.9 mm (5/8''):
≥ 1.0 mm *******
Thickness of insulation against heat 6 mm
Material of insulation against heat Polyethylene foam
Installation
height [m]
Additional refrigerant [kg]
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7
Minimum room area [m2]
0.6 9.0 10.5 12.5 14.5 17.0 19.5 22.0 25.0
1.8 1.0 1.5 1.5 2.0 2.0 2.5 2.5 3.0
2.2 1.0 1.0 1.0 1.5 1.5 1.5 2.0 2.0
Installation
height [m]
Additional refrigerant [kg]
1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5
Minimum room area [m2]
0.6 28.0 31.0 34.5 38.0 41.5 45.5 49.5 54.0
1.8 3.5 3.5 4.0 4.5 5.0 5.0 5.5 6.0
2.2 2.5 2.5 3.0 3.0 3.5 3.5 4.0 4.0
Installation
height [m]
Additional refrigerant [kg]
2.6 2.7 2.8
Minimum room area [m2]
0.6 58.0 63.0 67.5
1.8 6.5 7.0 7.5
2.2 4.5 5.0 5.0
29

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Nefit-Bosch Climate 5000 Multi Split wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Nefit-Bosch Climate 5000 Multi Split

Nefit-Bosch Climate 5000 Multi Split Bedienungsanleitung - Deutsch, Englisch, Holländisch, Dänisch, Französisch, Italienisch, Portugiesisch, Spanisch, Polnisch, Türkisch - 64 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info