619012
7
Zoom out
Zoom in
Vorherige Seite
1/8
Nächste Seite
nv Niko sa Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail: support@Niko.be — www.niko.be PMXXX-78100R08171
XXX-78100 SENSOR (XX-781)
1 2 3 4 5 6 7
Prog.
88
21:0°C
1. DESCRIPTION
ThissensorispartoftheNikosensor/actorproductrange.Thisrangeoffersanumberofcomfortfunctionsin
combination with different switch functions.
XXX-78100: clock thermostat 45 x 45mm (XX-781 + transition frame)
Attention:suitableonlyforindoormounting!
Sensor (A) = the visible electronic component, available in all Niko flush mounting designs and colours, which,
eitherautomaticallyoraftermanualoperation,sendsaswitchcommandtotheconnectedactor.
Actor (B) = the built-in component, which, upon receipt of a command from the connected sensor, switches
the connected load or transmits a Nikobus telegram.
2. TECHNICAL DATA
•Tobeusedincombinationwithactor420-0010X (09-7X1) or 420-0020X (09-7X2)
•Day/weekprogramming
•Settingprecision:±0.5°C
•30minpowerreserveincaseofpowercut,theprogramremainsinmemory
•Manualoperationpossible
•Max.settingof24switchmovements
•3typesoftemperaturelevels:day,night,andantifreezelevel
•Timeortemperaturedisplaycanbesetpermanently
•6speedselections:infunctionofthedimensionsofthelocation(RPvalue)
•Installationinstructions:
-mountingheight:±1,5m
- free air circulation
- not in direct sunlight
-notdirectlyexposedtoaheatingelement
•Ambienttemperature:0->40°C
•Storagetemperature:-25->75°C
Theactorsmayswitchupto1Awhenusedincombinationwithatemperaturesensor.Ifahigherpower
isswitched, the heating of the actorwilldisturbthe proper operation of the temperature sensor.The
thermostat is designed to control the control valves or an input contact of the central heating.
3. OPERATION
Thethermostathas aninternalPIcontroland
controls the heating system with pulse width
modulation(PWM).Thethermostatwilldistrib-
uteits controlover variouscycles. Depending
on the temperature measured, it can in the next
cyclecontrolthecontactfor10to100percent
ofthecycle.Thelengthofafullcycledepends
on the RP value (see setting RP value).
During installation, the following must be
taken into account:
•responsetimesofthecontrolvalves.Theseusuallyhavearesponsetimeof0-100%in3minutes.
•coolingperiodoftheboiler.Useabypassifnecessary.
4. DISPLAY AND OPERATING KEYS
Keys Function
increasesettemperature(insteps:pressbriefly;scrolling:presslong)
decreasesettemperature(insteps:pressbriefly;scrolling:presslong)
selecttheweekday
displayingandconfirmingcurrenttime
programming
displayingcurrenttemperature
RESET(Donotpressthispushbuttonwithsharp,metalobjects)
Thebuttons
and areintendedonlyforthefirstuseorfortheprogrammingoftheclockthermostat.
current weekday menu
1 = Monday programming
menu
time setting
setting the temperature
level menu
heating
temperature level indication: memory location active
sun = day temperature level
moon = night temperature level manual operation
ice crystal = antifreeze temperature level active
5. CONFIGURATION
Ifnooperationiscarriedoutduring30s.,thethermostatwillreturnautomaticallytothestartingscreen.After
±10min,theclockthermostatdisplaysthecorrecttemperature.
Basic settings
ThebasicsettingsalwayshavetobesetwhenusingthethermostatforthefirsttimeorafteraRESET.The
basicsettingsare:currentweekdayandhour,theRPvaluewhichdependsonthespaceandtheregulation
valueforday,nightandantifreezetemperature.
A. Setting the weekday and hour
WhenswitchingonthevoltageforthefirsttimeorafteraRESET,allsymbolsandsegmentsbrieflyappearon
thedisplay.Ifnohourisstored,theunitautomaticallydisplaysthesettingofthehourandweekdaymode.Time
andweekdayblink,youcanimmediatelygotostep2.
Step Action Result
1
Press for 3s
to activate mode for setting hour
andweekday.
Timeandweekdayblink.
2
Press
tosetweekday.
1=Monday,2=Tuesday…
3
Press
or to set the time.
•pressbriefly:settingoftheminutes
•presslong:phasesof5min,afterwardsbyhour
4
Press again
.
Return to starting screen
B. Setting the RP value
Notallheatinginstallationsreactatthesamespeed.Forthisreason,theswitchingon/offsequenceoftheinstal-
lationhastobeadaptedtothelocalcircumstances(regulationperiod).ThisisdonethroughtheRPvalue.
Theunit isprovided with6RP values,starting withRP1 forsmallareas (fastregulationperiod) upto and
includingRP6forlargeareas(slowregulationperiod).
RP value Minutes Application
1 4 smallrooms,electricalheating4...6°C/hour
2 8
3 12
4 16
5 20
6 24 largerooms,underfloorheating1...2°C/hour
Step Action Result
1
Press
and simultaneously.
Unit switches to RP setting.
2
Press
or to set RP value.
RP1;RP2;…;RP6
3
Press
.
Return to starting screen
C. Setting the temperature levels
Thetemperaturelevelsbelowarethestandardsettings.
Temperature level Symbol Standard setting Setting range
Day Sun +20°C betweennightleveland+30°C
Night Moon +15°C between+7°Canddaylevel
Antifreeze Icecrystal +7°C Fix value, cannot be set
Thesettingsofthedayandnightlevelcanbemodifiedasfollows:
Step Action Result
1
Press for 3s
.
Unit switches to programming.
2
Press
toselectdayornighttemperaturelevel.
Sunormoonappearontheleftsideofthedisplay.
3
Press
or .
Increase/decreasetemperatureby0.5°C.
4
Press
.
Return to starting screen
D. Setting the offset value
Therearecertainfactorsthatcanaffectthetemperaturemeasurement.Therecanbeadifferencebetween
thetemperaturestatedonthethermostatandtheactualtemperatureintheroom.Tocorrectthisdifference,
proceed as follows:
Waitforatleast10min,sothetemperaturestatedontheclockthermostatissteady.Thenreadthetempera-
ture in the room from a thermometer. If the temperature stated on the thermostat is lower / higher than the
temperaturestatedonthetermometer,youhavetosetapositiveresp.negativeoffsetvalue.Thisway,youcan
adjustthetemperaturefrom-6°Cto+6°C.
NOTE:toguaranteeasteadytemperature,settheoffsetvaluewhentakingthethermostatintouse.Thefabric
setting is 0.
Step Action Result
1
Press
, and simultaneously.
Devicewillgototheoffsetsetting.(indicationonthescreen:POd)
2
Press
or .
Increase/decreaseoffsetby0,5°C.
3
Press
.
Return to starting screen
Theoffsetvaluecanbesettoavaluebetween-6°Cbelowand+6°Cabovethestandardsetting.
6. USAGE
A. Setting the temperature manually (manual mode)
Itisalwayspossibleto change the temperature manually ifyouwishto deviate from the set temperature
level.Amanualactionisindicatedbyablinking‘handsymbol’onthedisplay.Atthesametime,thesymbol
‘thermometer’fortheindicationofthetemperatureleveldisappears.Afterafewseconds,theactualroom
temperatureisagaindisplayed.
Step Action Result
1
Press
or to increase/decrease temperature.
Desired temperature blinks.
2
Press
to confirm.
Return to starting screen, the current temperature
isdisplayed.
t
20°C
19°C
18°C
RELAY ON
100%
Cycle 1 Cycle 2 Cycle 3 Cycle 4 Cycle ...
100% 50% 30% 10% 10%
A
B
10A
R,L,C
420-0010X (09-7X1)
XXX-78100 (XX-781)
4A
R,L
420-0020X (09-7X2)
EXT1
20 : 0° C
7

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Niko XXX-78100 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info