to control the cooling capacity.
A potential-free contact provides
for remote enabling.
The unit is designed for outdoor
installation. Under certain
circumstances, it can also be used
in indoor areas.
The unit cooling cycle comprises
an evaporator, compressor,
electronic injection valve,
condenser, condenser fan, pressure
transducer, high and low pressure
switches and a 4-way changeover
valve for heating mode.
The medium cycle comprises
a tube bundle heat exchanger,
a circulation pump and a flow
switch.
Vibration dampers, cabled remote
controls and glycol concentrate are
available as accessories.
The units are shipped in sturdy
transport packaging. Immediately
check the units on delivery and
make a note of any damage or
missing parts on the delivery note.
Inform the forwarding agent and
contractual partner.
Claims under guarantee made
at a later date will not be accepted.
Unit description
Transportation and packaging
In cooling mode, the unit (an
air-cooled chiller) takes heat out
of the operating medium to be
cooled, water or a mixture of
water and glycol, within a closed
medium cycle in the evaporator
(plate heat exchanger) and passes
it on to the closed cooling cycle.
As a consequence of the heat
exchange, the medium cools and
the refrigerant in the cooling cycle
vaporises under low pressure.
The gaseous refrigerant
enters an electric compressor
(scroll construction) which
increases the pressure and the
temperature of the refrigerant.
The gaseous refrigerant is
led into a finned condenser,
which, as a consequence of
the heat exchange, condenses
the refrigerant under high
pressure to a liquid. The air
emerging at the condenser heats
the environment. The liquid
refrigerant is fed by means of
a variable injector valve back to
the evaporator where the circuit
begins again.
A return temperature dependent,
seamless controller, which ensures
the unit's operation and all of
the safety functions, is used
Intended use
Depending on the model and
the unit, the units are only
intended to be used as a chiller
for the cooling of the operating
medium water or a water-glycol
mixture within a closed medium
cycle.
Any different or additional
use is a non-intended use.
The manufacturer/supplier
assumes no liability for damages
arising from non-intended use.
The user bears the sole risk in such
cases.
Intended use also includes working
in accordance with the operating
and installation instructions and
complying with the maintenance
requirements.
Applicability
Within the course of continuous
further development of all
products, REMKO GmbH & Co.
KG reserve the right to carry
out technical changes
to the units as well as updates
to the documentation.
The documentation on the unit
(name plates, wiring diagrams,
etc.) shall be considered as part
of the overall documentation.
Ecological design directive
The regulation (EU) 2016/2281
(LOT 21) approved by
the European Commission is
the enforcement action for
the ecological design directive
2009/125/EC, whose principal
objective is to reduce the primary
energy demand in the European
Union by 2030 and to reduce
the emissions of hazardous
substances associated with this.
The chillers from REMKO
comply with the applicable
energy requirements from
the ecological design directive.
The product datasheet required
per the ordinance, to verify
ERP conformity is attached
as a separate document and is
also available for download from
www.remko.de.
Proper handling
Insofar as intervention is required
in the refrigerant circuit of the unit
during maintenance or repair
work, all work shall be carried
out exclusively by persons and
companies who have a certificate
in accordance with the prerequisites
of EC ordinance no. 517/2014
of the European Council.
5
5

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO RVS DC serie 50-80-130-180 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO RVS DC serie 50-80-130-180

REMKO RVS DC serie 50-80-130-180 Bedienungsanleitung - Deutsch - 44 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info