699073
93
Zoom out
Zoom in
Vorherige Seite
1/114
Nächste Seite
SATEL INTEGRA 91
signaling stops after the maximum duration of acoustic signaling elapses, even if the
control output is still active. The optical signaling is active as long as the output is active.
ASP-205 / ASP-215 both outputs control acoustic and optical signaling. Thus two different,
independently triggered ways of signaling can be configured. As a result, the outputs can
separately control the optical and acoustic signaling or trigger other signaling for different
alarms (e.g. burglary and fire). The command to start the signaling is sent to the siren only
during the response time. Therefore, the cut-off time for the control panel outputs which
control the siren must be longer than the response period. It is recommended that cut-off
time correspond to maximum duration of signaling programmed for the siren. The signaling
stops after the maximum duration of signaling elapses, even if the control output is still
active.
The zones to which the wireless siren is assigned are activated if a siren power supply
trouble occurs (select the appropriate reaction type for the zones):
ASP-105first zone: low battery; second zone: 12 V DC power loss.
ASP-205 / ASP-215both zones: low battery.
If the siren tamper is to trigger tamper alarm, program the zone as 2EOL/NC or 2EOL/NO.
The tamper information is sent immediately, while the trouble information during the
response time.
Tamper alarm on opening the tamper switch in the siren:
ASP-105 lasts for the maximum time of acoustic signaling programmed for the siren (sound
type selected during programming and optical signaling),
ASP-205 / ASP-215lasts 3 minutes (sound type 1 and optical signaling).
After starting the SERVICE MODE or TEST MODE and for 40 seconds after power-up, the
signaling in the siren is blocked. It enables installation work to be carried out. Opening
the tamper switch will not trigger loud signaling, but information on tamper will be sent
(when in service mode, the control panel will not signal the tamper alarms). The
command to block/unblock the signaling connected with starting / ending the test
mode or the service mode is sent during the response time.
9.3.3 Wireless expanders of hardwired zones and outputs
The wireless expander of hardwired zones and outputs (ACX-200 / ACX-201 / ACX-210 /
ACX-220) takes up 4 zones and 4 outputs in the system. You can configure the alarm system
zone/output to which expander zone/output is assigned in much the same way as hardwired
zones/outputs. You should remember however that sensitivity of the expander zones may be
different from that programmed in the control panel:
from 20 ms to 140 ms – the same as the value programmed in the control panel,
above 140 ms only some values are available: 400 ms, 500 ms, 700 ms, etc. every
200 ms (the programmed value is rounded up to that supported by the expander).
The EN50131-3 standard requires that zones must react to signals lasting more than
400 ms. Therefore, select 400 ms when programming sensitivity of the alarm zones.
Information on the state of zones and commands to change the state of outputs are sent
immediately. Zone settings are sent during the response time (in one period, data relating to
configuration of one zone are sent to the expander module, i.e. sending the information on
settings of four zones require four response periods).
If communication with the control panel is lost, all previously activated outputs will be
deactivated after 20 response periods.
Additionally, the ACX-201 expander module sends information about:
status of AUX1 and AUX2 power supply outputs information on overload is sent when
the AUX1 or AUX2 output load exceeds 0.5 A.
93

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Satel Integra 128 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Satel Integra 128

Satel Integra 128 Bedienungsanleitung - Deutsch - 54 seiten

Satel Integra 128 Zusatzinformation - Deutsch - 121 seiten

Satel Integra 128 Installationsanweisung - Deutsch - 38 seiten

Satel Integra 128 Bedienungsanleitung - Englisch - 51 seiten

Satel Integra 128 Installationsanweisung - Englisch - 36 seiten

Satel Integra 128 Kurzanleitung - Holländisch - 24 seiten

Satel Integra 128 Bedienungsanleitung - Holländisch - 52 seiten

Satel Integra 128 Zusatzinformation - Holländisch - 121 seiten

Satel Integra 128 Installationsanweisung - Holländisch - 35 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info