521718
5
Zoom out
Zoom in
Vorherige Seite
1/20
Nächste Seite
Siemens Building Technologies CM2N3204E / 1.1999
Landis & Staefa Division 5/20
20
22
24
26
18
16
14
12
t
Nmin
T [˚C]
R/A
t
T
T
R
A
Room temperature
limit
(DtPnt 12)
Outside temperature
limit
(DtPnt 13)
Night purging active
(DtPnt 15)
End of
occupancy time
Beginnning of
occupancy time
Delta
(DtPnt 14)
3204D04E
This function enhances comfort and optimizes energy consumption in rooms with vary-
ing occupancy levels. An integral CO
2
/VOC controller reduces the CO
2
or CO
2
/VOC
concentrations in the space. The P-band, the switching values for the fan speeds and
the design value at full occupancy are adjustable; the switching differential is 160 ppm.
Using the detectors connected to signal inputs Z, B1 and B2, the controller acquires the
actual temperature and CO
2
values. If the CO
2
or CO
2
/VOC concentrations in the
space exceed the switching value of fan speed I + ½SD, the temperature controller is
activated and the fan will run at speed I. The temperature controller maintains the prese-
lected setpoint (Comfort or Economy). If the CO
2
or CO
2
/VOC concentrations increase
further, fan speed II will be activated. Between this function and the step output of the
time switch program, maximum value selection takes place, with both functions having
the same priority. In the case of systems with recirculated air dampers, the damper
control function is activated also. Here, Y30 minimum limitation, recirculated air startup
mode and the frost protection controller with a higher priority act on the Y30 control sig-
nal.
Integral limit controller for HR equipment such as thermal wheel type heat exchangers,
plate heat exchangers, and glycol circuits: setpoint, P-band and integral action time are
adjustable. The limit controller is active only when the plant is in operation (fan speed I
or II).
Using the detectors connected to signal inputs Z, B1 and B2, the controller acquires the
actual temperatures. The manipulated variables delivered by the integral limit and tem-
perature controllers are compared with one another with the help of a priority selector,
which selects the manipulated variable with the smallest value (minimum selection).
This manipulated variable reduces the output of the HR equipment. Since a certain
amount of heat is not now available from the HR equipment, the balance is delivered by
a downstream air heater battery (terminal Y10).
For ventilating and air conditioning plants using hot water heating coils:
all values for frost protection (response temperatures, setpoints, P-bands, and integral
action times) are preset and can be changed. The temperature is acquired either in the
water circuit or at the air outlet of the hot water heating coil.
The protective actions are the following:
continuous opening of the heating valve, activation of the hot water circulator
deactivation of the fan or closing of the air dampers
maintaining the temperature when the fans are deactivated (only on the water side,
setpoint «Standby controller»)
fault status signal when there is risk of frost
Use of the following detectors is a prerequisite:
QAE22... or QAD22 for frost protection on the water side.
QAF63.2, QAF63.6 for frost protection on the air side.
Function diagram
Demand controlled
ventilation
Anti-icing protection for
HR equipment
Frost protection
(on the water or air side)
5

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

siemens-aerogyr-rwi65.02

Suche zurücksetzen

  • Kaltstart gemacht und die rote Alarmlampe leuchtet immer noch dauernd
    Eingereicht am 10-4-2022 12:01

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens AEROGYR RWI65.02 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens AEROGYR RWI65.02

Siemens AEROGYR RWI65.02 Bedienungsanleitung - Deutsch - 50 seiten

Siemens AEROGYR RWI65.02 Bedienungsanleitung und Installationsanweisung - Holländisch - 73 seiten

Siemens AEROGYR RWI65.02 Bedienungsanleitung - Französisch - 22 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info