Siemens Building Technologies CM2N3204E / 1.1999
Landis & Staefa Division 7/20
This function prevents freeze-ups of the hot water heating coil at low outside tempera-
tures (especially in plants that use on/off dampers).
The period of time preheating is active can be adjusted from 0 s to 10 min.
When the plant is switched on, first, only the hot water circulator (Q13/Q14) is activated
while the hot water valve (Y10) is fully open.
To protect the plant, fan speed II is disabled when outside temperature are very low. At
what outside temperature this function is activated depends on the value set (adjustable
from 50 °C to +150 °C). To prevent the controlled system from oscillating at greatly
varying outside temperatures, the RWI65.02 operates with a fixed hysteresis of 2 Kelvin.
This function is used in connection with outside air handling to save energy
(predominently in rooms with low occupancy levels).
The damper sequence (Y30) with operating action « / » is not implemented as a control
sequence. During plant operation, the damper is preset to a fixed position. The fixed
value of the manipulated variable for the air dampers is adjustable from 0 to 100 %
(Y30 minimum limitation).
For the hot water pump (DIL switch no. 8 must be in position «Hot water heating
coil»).
To avoid damage during plant off times, there are three setting choices available:
- the pump is permanently activated;
the pump is activated for 30 s at 24-hour intervals after the last operation, or
- the pump runs continuously when the outside temperature is below 5 °C; the
minimum pump running time (adjustable from 0 s to 30 min) is maintained
- the pump is periodically activated, that is, the pump is activated for 30 s after the
last operation according to the selected time (adjustable from 5 min to 24 h)
For the chilled water pump.
To avoid damage during plant off times, it is possible to select periodic pump run. If
this function is enabled (selectable), the pump will be activated for 30 s every after-
noon at 15.00.
Forced runup.
The fan is always started via the first speed. If the second speed is selected right from
the start, the first speed is first activated.
Switching to the second speed takes place only when the set time has elapsed
(adjustable from 0 to 5 min).
Rundown time.
When switching down from the second to the first speed, the RWI65.02 deactivates
the second speed, and the first speed is activated only when the preset time has
elapsed (adjustable from 0 s to 5 min).
In plants that use hot water heating coils:
- continuous checkback signals on the operational status of the plant and on the
status of the hot water circulator, based on the signals received from supervisory
elements such as flow switch and overload protection
- continuous supervision of risk of frost
- switching on and off depending on the selected alarm priority («A» or «b»)
In plants that use electric heater batteries:
- continuous checkback signals on the operational status of the plant and, especially,
on that of the electric heater battery, based on the signals received from supervisory
elements such as flow switch, overload and overtemperature protection
- switching on and off depending on the selected alarm priority («A» or «b»)
Preheating time
Disabling of fan speed II at
low outside temperatures
Fixed preset damper
position
Periodic pump run
(pump kick)
Forced runup and
rundown time for fans
Supervision
7

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

siemens-aerogyr-rwi65.02

Suche zurücksetzen

  • Kaltstart gemacht und die rote Alarmlampe leuchtet immer noch dauernd
    Eingereicht am 10-4-2022 12:01

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens AEROGYR RWI65.02 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens AEROGYR RWI65.02

Siemens AEROGYR RWI65.02 Bedienungsanleitung - Deutsch - 50 seiten

Siemens AEROGYR RWI65.02 Bedienungsanleitung und Installationsanweisung - Holländisch - 73 seiten

Siemens AEROGYR RWI65.02 Bedienungsanleitung - Französisch - 22 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info