Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.5.2 Compensating and auxiliary variables
Also refer to "3.3.3 Compensating variables".
The ECO automatic energy saver necessitates an outside sensor. As compensating
and auxiliary variables, it takes into account the development of the outside tempera-
ture and the building's heat storage capacity. The following parameters are considered:
the building's time constant
the actual outside temperature (T
A
)
the attenuated outside temperature (T
AD
). Compared to the actual outside tempera-
ture, the attenuated outside temperature is significantly dampened.
This ensures that no heating will be provided in the summer by making certain that
the heating will not be switched on during a few cool days
the composite outside temperature (T
AM
). Since the composite outside temperature
is attenuated, it represents the impact of short-term variations of the outside tem-
perature on the room temperature as they often occur during intermediate seasons
(spring and autumn)
By considering the attenuated outside temperature, the ECO automatic energy saver
takes into account the thermal inertia of the building should temperature variations
occur.
3.5.3 Heating limit
The ECO automatic energy saver requires a heating limit to set an ECO temperature in
the range –10…+8 K. From this setting value and the room temperature setpoint, the
heating limit is calculated.
3.5.4 Mode of operation of ECO function 1
ECO function 1 operates as an automatic summer / winter switch. The heating will be
switched off (mixing valve closes or burner off, heating circuit pump off) when the at-
tenuated outside temperature exceeds the heating limit.
It is switched on again as soon as all three outside temperatures have fallen below the
heating limit by an amount equal to the switching differential.
The heating limit is determined as follows:
Heating limit = w
N
+ T
ECO
(normal setpoint plus ECO temperature)
A room temperature setpoint w
N
of +20 °C and an ECO temperature T
ECO
of –5 K give
a heating limit of +15 °C.
3.5.5 Mode of operation of ECO function 2
ECO function 2 operates as an automatic 24-hour limit switch. The heating will be
switched off (mixing valve closes or burner off, heating circuit pump off) when the actual
or the composite outside temperature exceeds the heating limit.
It is switched on again as soon as all three outside temperatures have fallen below the
heating limit by an amount equal to the switching differential.
The heating limit is determined as follows:
Heating limit = w
akt
+ T
ECO
(current setpoint plus ECO temperature)
In contrast to ECO function 1, it is taken into consideration here when a reduced tem-
perature level is maintained.
A room temperature setpoint w
akt
of +18 °C and an ECO temperature T
ECO
of –5 K give
a heating limit of +13 °C.
In the case of protection mode, the ECO function does not use a setpoint, but a fixed
value. Also, the heating limit has a minimum limitation. It cannot be lower than 2 °C.
The heating limit is determined as follows:
5 + T
ECO
(fixed value of 5 °C plus ECO temperature)
Note
Example
Example
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP201 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP201

Siemens RVP201 Installationsanweisung - Deutsch, Englisch, Holländisch, Dänisch, Französisch, Italienisch, Spanisch, Schwedisch, Finnisch - 26 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info