Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.6 Frost protection for the plant and the building
3.6.1 Frost protection for the plant
Frost protection for the plant provides protection against freezing by activating the heat-
ing circuit pump, if controller and heat generating equipment are ready to operate
(mains voltage present).
Frost protection for the plant can be provided with or without an outside sensor. The
switching differential is 1 K (fixed value).
Frost protection is always active, even if the control is switched off (operating modes
and
), with quick setback, and with Off through ECO.
If desired, frost protection for the plant can be deactivated with the coding switch “Frost
protection”.
Frost protection for the plant is accomplished in two steps:
1. If the outside temperature falls to 1.5 °C, the heating circuit pump will be activated
for 10 minutes at 6-hour intervals.
2. If the outside temperature falls to –5 °C, the heating circuit pump will be activated
and runs continuously.
The frost protection stage active at a time will be switched off when the outside tempera-
ture has exceeded the limit value by an amount equal to the switching differential of 1 K.
Frost protection for the plant is accomplished in two steps:
1.
If the flow temperature falls to 10 °C, the heating circuit pump will be actuated
for 10 minutes at 6-hour intervals.
2.
If the flow temperature falls to 5 °C, the heating circuit pump will be actuated
and runs continuously.
The frost protection stage active at a time will be switched off when the flow temperature
has exceeded the limit value by an amount equal to the switching differential of 1 K.
3.6.2 Frost protection for the building
Frost protection for the building protects the rooms from excessively low temperatures.
It acts in all operating modes as a minimum limitation of the room temperature. It can
be achieved with or without room unit, provided the heating curve slope is correctly set.
The frost protection for the building is given higher priority over the ECO automatic
energy saver. If desired, frost protection for the building can be deactivated with the
coding switch “Frost protection”.
Without room unit:
Attenuated outside temperature 5 °C: the control is switched on and the flow
temperature is controlled such that a room temperature of 5 °C will be maintained
Attenuated outside temperature >6 °C: the control is switched off
With room unit and with quick setback active:
Room temperature 5 °C: the control is switched on and the flow temperature is
controlled such that a room temperature of 5 °C will be maintained
Room temperature >6 °C: the control is switched off
With room unit, but without quick setback:
Same as without room unit
With outside sensor
Without outside sensor
24

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP201 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP201

Siemens RVP201 Installationsanweisung - Deutsch, Englisch, Holländisch, Dänisch, Französisch, Italienisch, Spanisch, Schwedisch, Finnisch - 26 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info