Purging time
If the temperature on the collector sensor increases within a minute by the value defined under “increase”, the solar circulation
pump will be turned on for the set “purging time so that the medium to be measured is transported to the collector sensor. If when
the set ΔT is reached this does not switch on, a 5-minute circulation pause time for the starting aid function will apply.
Increase
If the temperature at the collector reaches within a minute the value defined, the solar pump is turned on for the duration of the
purging time.
Protective functions for Solar
The protection functions for Solar are not displayed in the “Protective functions” menu, but rather as a sub-menu in the
settings from the solar function, see " Solar " on page 35.
System protection
Priority protection function
The system protection should prevent an overheating of the components installed in the system through the forced shut down of
the solar circulation pump. If the value “AS Ton” on the collector has been exceeded for 1 Min. the pump will be turned off and not
turn on again in order to protect the collector, for example, from steam. The pump is turned on again when the value “AS Toff” on
the collector has not been met.
With the system protection (on), there are increased standstill temperatures in the solar collector and therefore an
increased pressure in the system. The operating manuals from the system components must be observed.
Collector protection
Priority protection function
The collector protection prevents the collector from overheating. A forced switching of the pump makes sure that the collector is
cooled through the storage. If the value “KS Ton” is exceeded on the collector, the pump will be turned on in order to cool the col-
lector. The pump is shut down if the value “KS Toff” on the collector is not met or the value “KS Tmax Sp.” on the storage or KS SB
Max on the pool is exceeded.
System protection has priority over collector protection! Even if the switch requirements for the collector protection are
present, the solar circulation pump is turned off once “AS T on is reached. Normally the values from the system pro-
tection (depending on the maximum temperature of the storage or other components) are higher than the collector pro-
tection.
Recooling
In the system hydraulics with solar, excess energy is guided from the storage back to the collector with an activated return cooling
function. This only occurs if the temperature in the storage is greater than the value “Return cooling Tref” and the collector is at
least 20 °C colder than the storage and until the storage temperature has fallen below the value “Return cooling Tref”. For muti-
storage systems, the return cooling applies to all storage.
Energy is lost through the collector through this function! The recooling should only be activated in cases of exception,
with low heat acceptance, for example, during vacation.
Frost Protection
A 2-level frost protection function can be activated. In level 1, the controller turns on the pump every hour for 1 minute if the col-
lector temperature is below the set value “Frost Level 1”. If the collector temperature continues to decrease to the set value “Frost
Level 2”, the controller will turn on the pump without disruption. If the collector temperature exceeds the value “Frost level 2 by 2
°C, the pump will turn off again.
Energy is lost through the collector through this function! It is normally not activated for solar systems with antifreeze.
The operating manuals from the other system components must be observed.
Collector alarm
If this temperature at the collector sensor is exceeded when the solar pump is turned on, a warning or error notification is
triggered. There is a corresponding warning in the display.
Collector
Collector sensor
The collector sensor can be determined or changed here. The collector sensor set here is used for solar function ( Tmin collector,
∆T Solar,....) as well as all protection functions Solar (collector protection, system protection, ...).
Solar storage
The solar storage sensor can be determined or changed here. The solar storage sensor determined here is used for the solar
function ( Tmax storage, ∆T Solar,....).
36
36

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Sorel XHCC S61 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Sorel XHCC S61

Sorel XHCC S61 Bedienungsanleitung - Deutsch - 44 seiten

Sorel XHCC S61 Bedienungsanleitung - Französisch - 44 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info