HEATER STAND AND LOCATION
- The heater is primarily for outdoor use only.
- Always ensure that adequate fresh air ventilation is provided.
- Always maintain proper clearance to combustible materials, i.e.
top 100cm and sides 100cm minimum.
- Heater must be placed on level firm ground.
- Never operate heater in an explosive atmosphere like areas
where gasoline or other flammable liquids or vapors are stored.
GAS REQUIREMENTS
- Use propane, butane, propane and butane mixture.
- The pressure regulator and hose assembly must be used conform local standard codes.
- Use correct pressure regulators conform to local regulation in force and specification of this manual.
- The installation must be conform local codes, or in the absence of codes, with the standard for storage and
handling of liquid petroleum gases.
- A dented, rested or damaged propane tank may be hazardous and should be checked by your tank supplier.
- Never use a propane tank with a damaged valve connection.
- The propane tank must be arranged to provide for vapor withdrawal from the operation cylinder.
- Never connect an unregulated propane tank to the heater.
- The rubber hose which connect the regulator and inlet should not be longer than 60 cm
- The rubber hose should have CE approval, and heat resistance should be between 20℃ to 80℃
LEAKAGE TEST
- Gas connections on the heater are leak tested at the factory prior to shipment.
- A complete gas tightness check must be preformed at the installation site due to possible mishandling in
shipment or excessive pressure being applied to the heater.
- The heater must be checked with a full cylinder.
- Make sure the safety control valve is in the OFF position.
- Make a soap solution of one part liquid detergent and one part water. The soap solution can be applied with a
spray bottle, brush or rag.
- Soap bubbles will appear in case of a leak.
- Leakage test points. See pictures below.