10. Maintenance
The product does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture
and oil/soot/vapours, and keep the device clean.
11. Error Indications
With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your
Victron Energy supplier.
11.1 General error indications
Problem
Cause
Solution
No output voltage on AC-out-2.
EasySolar-II GX in inverter mode
Unit will not switch over to generator or
mains operation.
Circuit breaker or fuse in the AC-in input
is open as a result of overload.
Remove overload or short circuit on AC-
out-1 or AC-out-2, and reset fuse/breaker.
Inverter operation not initiated when
switched on.
The battery voltage is excessively high or
too low. No voltage on DC connection.
Ensure that the battery voltage is within
the correct range.
'Low battery' The battery voltage is low.
Charge the battery or check the battery
connections.
'Low battery' (Shutdown)
The converter switches off because the
battery voltage is too low.
Charge the battery or check the battery
connections.
'Overload'
The converter load is higher than the
nominal load.
Reduce the load.
'Overload' (Shutdown)
The converter is switched off due to
excessively high load. Reduce the load.
'Over Temperature' The environmental temperature is high,
or the load is too high.
Install the converter in cool and well-
ventilated environment, or reduce the
load.
'Low Bat V Overload' (Shutdown) Low battery voltage and excessively high
load.
Charge the batteries, disconnect or
reduce the load, or install higher capacity
batteries. Fit shorter and/or thicker
battery cables.
'High DC Ripple' Ripple voltage on the DC connection
exceeds 1,5Vrms.
Check the battery cables and battery
connections. Check whether battery
capacity is sufficiently high, and increase
this if necessary.
'DC Ripple Shutdown'
The inverter is switched off due to an
excessively high ripple voltage on the
input.
Install batteries with a larger capacity. Fit
shorter and/or thicker battery cables, and
reset the inverter (switch off, and then on
again).
The charger does not operate. The AC input voltage or frequency is not
within the range set.
Ensure that the AC input is between
185VAC and 265VAC, and that the
frequency is within the range set (default
setting 45-65 Hz).
Circuit breaker or fuse in the AC-in input
is open as a result of overload.
Remove overload or short circuit on AC-
out-1 or AC-out-2, and reset fuse/breaker.
The battery fuse has blown.
Replace the battery fuse.
The distortion or the AC input voltage is
too large (generally generator supply).
Turn the settings WeakAC and dynamic
current limiter on.
The charger does not operate. 'Bulk
Protection' shown.
EasySolar-II GX is in 'Bulk protection'
mode thus, the maximum bulk charging
time of 10 hours is exceeded. Such a long
charging time could indicate a system
error (e.g. a battery cell short-circuit).
Check your batteries. NOTE: You can reset
the error mode by switching off and back
on the EasySolar-II GX. The standard
EasySolar-II GX factory setting of the 'Bulk
protection' mode is switched on. The
'Bulk protection' mode can be switched
off with help of VEConfigure only.
The battery is not completely charged. Charging current excessively high,
causing premature absorption phase.
Set the charging current to a level
between 0.1 and 0.2 times the battery
capacity.
Poor battery connection.
Check the battery connections.
The absorption voltage has been set to
an incorrect level (too low).
Set the absorption voltage to the correct
level.
The float voltage has been set to an
incorrect level (too low).
Set the float voltage to the correct level.
The available charging time is too short
to fully charge the battery.
Select a longer charging time or higher
charging current.
The absorption time is too short. For
adaptive charging this can be caused by
Reduce the charging current or select the
'fixed' charging characteristics.
17

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info