3.11.5 Timer
- The timer block is used to cretate a daily program to
initialise the operation time of the extra output (P3), this
function is generally use for energy saving in the case of an
additional heat source being used to warm the tank (e.g.:
additional heat is present only at the end of the day if the
sun loading was insufficient during the day.)
To use the Timer function select the line “Timer” and choose
“Yes”, then there is the possibility of adjusting the “start” and
“stop” times for three blocks.
3.12 Cooling Function
Available only if extra function “coolingis selected on the
output P3
3.12.1 Cooling start
- setting level to start cooling the tank1 (by activating P3
output) to another heat storage for example when the water
temperature in the top of tank1 (T3) is above this setting
level. (Adjustable 20 to 90°C with factory value 75°C)
3.12.2 Cooling hysteresis
- Value of the hysteresis to stop cooling the tank1 when the
water temperature on the top of tank (T3) is under Cooling
start temperature minus hysteresis value. (Adjustable 1 to
30°C with factory value 10°C)
3.13 Diff control Function
Available only if extra function “diff controlis selected on the
output P3.
3.13.1 Max cold tank
- Maximum level on tank1 to stop the exchange function (T3
= TC).
(Adjustable 15 to 95°C with factory value 65°C)
3.13.2 Min warm tank
- Minimum level on external tank to start the exchange
function (T4 = TW). (Adjustable 0 to 95°C with factory value
15°C)
3.13.3 dTMax
- Value of the difference between cold and warm storage to
start the exchange function. (Adjustable 3 to 40°C with
factory value 15°C)
3.13.4 dTMin
- Value of the difference between cold and warm storage to
stop the exchange function. (Adjustable 2 to 30°C with
factory value 7°C)
3.14 Antistagnation Function
Available only if extra function “Antistagnationis selected on
the output P3.
3.14.1 Start Level
- Setting level on collector (T1) to start the function, the
pump P1 will be turned on to discharge the warm
temperature of the collector through the relay P3.
(Adjustable 0 to 200°C with factory value 110°C)
3.14.2 Stop Level
- Setting level on collector (T1) to stop the antistagnation
function, the pumps P1 and P3 will be turned off. (Adjustable
0 to 150°C with factory value 90°C)
4 Operation Menu
4.1 Automatic and Off operation
- To put your system in Automatic operation, press (+) or (-) to
select the “Automatic“ line and press (►) to active this
working mode.
- To put your system in Off mode repeat the same sequence
as above.
Note: The controller status is displayed by a small graphic, on
the main screen stating “OFF”
 Settings -
Delay +900s
Timer On
Time 1 Start 24H00
Time 1 Stop 24H00
Time 2 Start 24H00
Time 2 Stop 24H00
Time 3 Start 24H00
Time 3 Stop 24H00
Water temperature on top of tank1 T3
C)
Cooling stop
(start hysteresis)
Cooling
start
P3
Warm storage TW
Cold storage TC
MinWarm
tank
MaxCold
Tank
Extra
P3
dTMin
dTMax
Collector
(T1°C)
Stop level
Start level
P1
Tank (T2°C)
P3
Standard
loading cycle
Antistagnation
cycle
 Operation--------------- -- -----
Automatic (Active)
OFF
Chimney sweep
Manual testing
15

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Watts Solar Controller LCD PLUS wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info