clear any soot falls which may have occurred due to the difference in combustion between the stove and the open fire.
If there is no existing chimney then either a prefabricated block chimney in accordance with Building Regulations
Approved Document J or a twin walled insulated stainless steel flue to BS 4543 can be used. These chimneys must
be fitted in accordance with the manufacturer’s instructions and Building Regulations.
A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not suitable for using for the
complete chimney. The chimney and connecting fluepipe must have a minimum diameter of 150 mm and its
dimension should be not less than the size of the outlet socket of the stove.
Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends should not be used.
If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternatively a
draught stabiliser should be fitted. The adjustable flue damper should not close off the flue entirely but should in its
closed position leave a minimum continuous opening free area of at least 20% of the total cross sectional area of
the flue or fluepipe.
Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and
connecting flue pipe.
Distance to Combustible materials
Combustible materials should not be located where the heat dissipating through the walls of fireplaces or flues could
ignite it. Therefore when installing the stove in the presence of combustible materials due account must be taken of
the guidance on the separation of combustible material given in Building Regulations Approved Document J and also
in these stove instructions.
UNIQ36 /
UNIQ36 Pedestal
UNIQ37 /
UNIQ37 Pedestal / UNIQ37 Large
Distance to combustible materials rear 175 mm 100 mm
Distance to combustible materials side 450 mm 600 mm
Distances to flammable materials/furnitures 1150 mm 825 mm
Hearth
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not
independently supported.
The Westfire UNIQ36/ WF36 Pedestal and UNIQ37/ WF37 Pedestal wood stoves has been tested and is suitable to
be installed on a 12 mm non combustible plate such as Westfire 12 mm glass plates or 20 mm slate plates. Installa-
tion of all hearths should comply in size and construction so that it is in accordance with the provisions of the current
Building Regulations Approved Document J.
The clearance distances to combustible material beneath, surrounding or upon the hearth and walls adjacent to the
hearth should comply with the guidance on the separation of combustible material given in Building Regulations
Approved Document J and also in these stove instructions.
If the stove is to be installed on a wooden floor, it must be covered with a non-combustible material at least 12 mm
thick, in accordance with Building Regulations Approved Document J, to a distance of 30 cm in front of the stove and
15 cm to each side measuring from the door of the combustion chamber.
Combustion air supply
In order for the stove to perform efficiently and safely there should be an adequate air supply into the room in which
the stove is installed to provide combustion air. This is particularly necessary if the room is double-glazed or a flue
draught stabiliser is operating in the same room as the appliance. The provision of air supply to the stove must be in
accordance with current Building Regulations Approved Document J. An opening window is not appropriate for this
purpose. Air inlets must be positioned in such a way that they cannot be blocked. An air inlet may be a vent (the vent
must be open and the capacity of the vent sufficient when the stove is lit) or a fresh air system linked to the stove.
There are no European rules regarding the minimum distance to non-flammable walls, Westfire recommend leaving
a gap of at least 10 cm behind and to sides of stove.
11

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Westfire WF36 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info