Eliminate fault
Sense ll – 6 720 812 775 (2014/10)
Problem Cause Remedy
Required room
temperature
not achieved.
Thermostatic valves
on the radiators are
set too low.
Set the thermostatic
valves higher.
Temperature for
heating mode is set
too low.
Set the temperature
for heating mode
higher.
System in summer
mode.
Switch system over
to winter mode
( Chapter 5.3.4,
page 25).
Flow temperature
controller on heat
source set too low.
Set the flow
temperature higher
( operating
instructions for the
heat source).
Air in the heating
system.
Bleed the radiators
and the heating
system.
Installation location
of the outdoor
temperature sensor
is not optimal.
Contact Installer to
install the outside
temperature sensor
at a suitable
installation location.
Required room
temperature
greatly
exceeded.
Radiators become
too hot.
Set thermostatic
valves in adjoining
rooms lower.
Set temperature for
the operating mode
concerned lower.
Set temperature for
all operating modes
lower.
If the controller is
installed in the
reference room, if
the installation
location of
controller is
unfavourable,
e.g. external wall,
close to window, in
a draught ...
Contact Installer to
install the controller
at a suitable
installation location.
Table 39 Eliminating "sensed" faults
Excessive room
temperature
fluctuations.
Temporary
influence of external
heat on the room,
e. g. from solar
exposure, room
lighting, TV,
fireplace etc.
Contact Installer to
install the controller
at a suitable
installation location.
Temperature
rises instead of
dropping.
Incorrect time set. Reset the time
Room
temperature
too high during
setback mode.
The building retains
a lot of heat.
Set an earlier
switching time for
setback mode.
DHW cylinder
does not heat
up.
DHW temperature1)
on heat source set
too low.
Set the DHW
temperature1)
higher.
DHW temperature1)
on heat source not
set too low.
Contact Installer to
check the settings on
the controller.
If the DHW system is
controlled via a
module: Flow
temperature1) on
heat source set too
low.
Set flow
temperature1)
higher.
DHW program
incorrectly set.
Set DHW program.
The DHW heating
configuration does
not suit this heating
system.
Contact Installer to
check the settings on
the controller.
The DHW at the
draw-off points
is not reaching
the required
temperature.
Mixer set lower than
the required DHW
temperature.
If you are in doubt,
contact your Installer
to come and check
the mixer setting.
0 is displayed
constantly in
the info menu
under solar
yield even
though the
solar system is
in operation.
Solar system set
incorrectly.
Contact Installer to
check the settings on
the controller.
1) See operating instructions of the heat source for further
information.
Problem Cause Remedy
Table 39 Eliminating "sensed" faults
40

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Worcester-Bosch Greenstar Sense ll wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info