Operation and maintenance manual - EN
EN
www.atmos.cz EN-67
• Parameter S62 – characterizes the function for control of the air valve (flap) with actuator (servo
drive) located in the pellet burner. This valve is operated from the outlet of the burner discharge fan
via the AD04 module integrated in the burner (from serial production - default configuration). The
function is intended for models DCxxGSP, DCxxSP(X), CxxSP, ACxxSP (Model since 2018)... (1)
a) S62 = 0....... funkce OFF (for burners without flap with actuator)
b) S62 = 1....... function ON (for burners with flap with actuator - for models DCxxGSP and
DCxxSP(X), CxxSP, ACxxSP (Model since 2018))
(Burners equipped with internal flap with actuator with AD04 module and the third (additional)
2-pins connector.)
• Parameter S63 – characterizes the function of start delay of the pellet burner (AUTOSTART),
with function of automatic burner start after burnout of the wood. Start delay of the pellet burner
we use in case, that the operator wants to switch the selector switch from the position - wood
to the position - pellets immediately after firing up without waitng till the boiler ran at nominal
output (TSV and TK temperatures not reached). This will always delay the start of the burner
60/120/180/240 minutes. When activating this function the display of the burner shows the time
remaining until the automatic start of the pellet burner (cold condition) or until the change to the
normal function of automatic start characterized with the parameter S34.
In case of that the operation waste gas temperature will be reached (parameter S36 = TSV + 20 K) ends
the countdown of the automatic start and the burner goes directly to normal auto start (parameter S34).
a) S63 = OFF... function switched off - factory stetting
b) S63 = 1... start delay of 1 hour (60 min) - recommended setting
c) S63 = 2... start delay of 2 hour (120 min)
(Setting possibility S63 = OFF, 1 (60 min), 2 (120 min), 3 (180 min), 4 (240 min))
This special function is active in the program version 38 and newer.
INFO - when putting burner into operation with activated function S63 = 1 (or 2, 3, 4) the
plumber may once enter the code 1111 and to skip from AUTOSTART directly to the burner
START (TSV and TK below than defined).
• Parameter S64 - characterizes the temperature of flue gas inside the heat exchanger of the boiler.
It serves to diagnoses the absense of pellets in the boiler tank or shows low output of the boiler. It
is not temperature of flue gas. Function is only for DxxPX (PXxx) boilers, burner profile A25PX.
Do not change… (130 °C)
Parameter S65 - characterizes start up time of the burner in OPERATION mode during which has
to be reached minimal waste gas temperature in the heat exchanger of the boiler set by parameter
S64.
If in this time the boiler does not reach temperature the display shows ALARM SETTINGS –
REFILL PELLETS. In such case check the set output in parameters T4 and T6 and increase it.
In case of low pellets level in the tank fill up the fuel. Function is only for DxxPX (PXxx) boilers,
burner profile A25PX. Do not change… (120 min)
67

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Atmos A25 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Atmos A25

Atmos A25 Bedienungsanleitung - Deutsch - 70 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info