554835
13
Zoom out
Zoom in
Vorherige Seite
1/22
Nächste Seite
Installation manual: Oasis security system JA-80K - 13 - MKE51801
12.17. Exit delay beeps while partially setting
(arming)
The exit delay caused by partial setting, e.g. using the A or B
key, can also be indicated by keypad beeps and internal-siren
beeps. The beeps get faster in the last 5 seconds.
3 4 1 Beeps enabled
3 4 0 Beeps disabled
Factory default setting: Beeps disabled.
12.18. Entrance delay beeps
The entrance delay can be indicated by keypad beeps and
internal-siren beeps:
3 5 1 Beeps enabled
3 5 0 Beeps disabled
Factory default setting: Beeps enabled
12.19. Setting (arming) confirmation by wired-siren
chirp
A hard-wired siren connected to the IW terminal of the control
panel can audibly indicate setting by one beep, unsetting by two
beeps and unsetting after an alarm by three beeps. Four beeps
mean an invalid attempt at setting the system has occurred.
3 6 1 Chirps enabled
3 6 0 Chirps disabled
Note: In JA-80L wireless sirens, this function can be individually enabled
for each siren. (see the siren manual).
Factory default setting: Hard-wired siren chirps disabled
12.20. Sirens always sound during audible alarms
Using this sequence it is possible to disable internal and external
sirens (IW and EW) if any part of the system is unset (partial
setting), i.e. when someone is home.
3 7 1 Sirens always sound during audible alarms
3 7 0 Sirens only sound during audible alarms when all
sections are set, i.e. no one is home
Factory default setting: Sirens always sound during audible
alarms.
12.21. Wireless siren alarm enabled (IW and EW)
This setting is for enabling and disabling wireless sirens in the
system:
3 8 1 wireless sirens enabled
3 8 0 wireless sirens disabled
Note: This setting has no effect on wired output terminals.
Factory default setting: wireless sirens enabled
12.22. Auto-bypass user approval via the key
The system has a built-in auto-bypass function so that if any
number of detectors are being triggered during setting (arming)
then they will be bypassed and ignored automatically.
If auto-bypass approval by the user is disabled, then during
setting (arming) the system notes which detectors are currently
triggered and automatically bypasses them without consulting
the user.
If however, auto-bypass user approval is enabled, then during
setting (arming), the system notes which detectors are currently
triggered and displays informative text on the keypad and only
bypasses them if the user approves the bypassing by keying in a
within 6 seconds of being notified.
3 9 1 Approval is requested from the user
3 9 0 Bypassing occurs automatically without user approval
Notes regarding setting the system with (a) triggered detector(s):
Details on currently triggered detectors can be viewed by pressing the
? key (e.g. open doors or windows).
If a wireless keyfob is used to set the system and auto-bypass user
approval is enabled, the system will set without bypass approval, i.e.
setting by keyfob does not trigger an approval request.
The automatic bypass of a detector will end after the detector has
been de-triggered (for example if a door is closed)
If auto-bypass user approval is enabled and Service mode is being
exited while a detector is being triggered, the installer will be notified
about the bypass. The installer can then approve the bypass by
pressing # twice.
To comply with the EN-50131-1standard 391 should be set.
Factory default setting: Bypassing occurs automatically
without user approval
12.23. Final-door detectors
In this mode, up to 5 detectors can be defined as final-door
detectors and assigned to addresses 01 to 05 or 46 to 50 in
order to make leaving a building much easier, especially via a
garage:
65x
where x: 0 = none,
1 = detectors on addresses 01 to 05,
2 = detectors on addresses 46 to 50
Description of final-door detector mode:
If a final-door detector is used in the system then the value of
x for exit delay programming is multiplied by 30 s (see 12.1)
thereby extending the delay, and if an entrance delay is
triggered by a final-door detector then the value of x for the
entrance delay is also multiplied by a larger value of 30 s.
A final-door detector should be programmed to have a natural
reaction.
Door/window detectors, hard-wired control panel inputs or
hard-wired inputs in the wireless keypad unit can be used as
final-door detectors.
If a final-door detector is used for a garage door, no instant
detectors should be inside the garage. Next-delay detectors
would however be acceptable.
Setting (arming) the system with a final-door detector
After entering a request to set the system, an exit delay of
between 30 to 270 seconds will begin and be indicated.
If a final-door detector is triggered during the exit delay, the
exit delay will be extended by the time in which the detector is
still triggered. So, if for example, the door is left continuously
open, the exit delay will never end.
If a final-door detector is de-triggered, the system will wait five
more seconds during which beeping gets faster, and if the
door is not opened again during this short period, the exit
delay will terminate and the system will be set immediately.
The duration of the exit delay therefore depends on the time
the final door stays open. For instance, in winter if the
driveway in front of a garage needs to be cleared of snow
there will be plenty of time to do it, and in summer when
garages can be exited easily and therefore quickly, the exit
delay can be rather shorter. The exit delay only depends on
the length of time the garage door is left open.
If no final-door detectors are triggered during the exit delay,
the system will provide an exit delay and then set.
If the final door detector stays continuously triggered, an
endless exit delay will result with the system never being set.
This means all delayed and next-delayed detectors will not be
set (armed).
If there are multiple final-door detectors in the system, the exit
delay is extended if any of them is triggered and ends after all
final-door detectors have been de-triggered.
13

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Jablotron JA-80K wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Jablotron JA-80K

Jablotron JA-80K Bedienungsanleitung - Englisch - 1 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info