3 HOW IT WORKS
3.1 SOURCE PRIORITY
The Mass Systemswitch switches the right AC power
source to the output(s). Therefore the Mass Systemswitch
is equipped with a source priority. If more than one AC
power source is available, the source with the highest
priority is switched to the output(s).
See figure 1. The generator input has the highest priority:
when generator power is available, all outputs (except the
inverter only output) are supplied by the generator. Power
on the shore input and/or the inverter input will be denied
even when they are available.
The shore input has the second priority. If there is no
generator power available, shore power will be transferred
to the power output and the short break output. Power on
the inverter input will be denied.
The lowest priority is assigned to the inverter. AC power
on the inverter input is transferred to the short break
output only when no other power source is available.
3.2 AC INPUTS
Three AC-sources can be connected to the Mass
Systemswitch:
Inverter power (IN3)
Shore power (IN2)
Generator power (IN1)
3.2.1 Only inverter power available
When there is no AC power available on the generator
input or the shore input, power from the inverter input is
transferred to the short break output only. The power
output and the generator only output are unavailable now.
The Mass Systemswitch is in a neutral state and
consumes no energy itself.
3.2.2 Shore power available
When there is no generator power available but AC power
is available on the shore input, the Mass Systemswitch will
supply both the power output and the Short break output
with AC power from the shore input. The generator only
output is unavailable now.
Figure 1: principle schematics of the Mass Systemswitch
3.2.3 Generator power available
When the generator is started, a control circuit samples its
output voltage and frequency. Only when both are within
allowed limits for approximately 10 seconds, the Mass
Systemswitch transfers the power from the generator input
to all outputs (except for the inverter only output).
Too low generator frequency and voltage may cause
damage to both the generator and the connected load.
Therefore AC power on the generator input is continuously
checked by a control circuit. If the generator frequency or
voltage is too low, generator power is immediately cut off
from the load.
The 10 seconds time delay provides an ‘easy start up’ for
the generator. This increases the generator’s lifetime.
3.3 AC OUTPUTS
The Mass Systemswitch has the following AC-outputs:
Inverter only output
Short break output
Power output
Generator only output
5

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Mastervolt Mass Systemswitch 16 kW wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info