CAUTION
CAUTION
-76 c mHg
Lo-lev er
Hi-leve r
Charg e hos e
Charg e hos e
Vac uum p ump
Lo-lev er
Manifo ld valv e
Multi-m eter
Pressu re meter
Fig.8-7
Additional Refrigerant Charge
8.3
Refrigerant cannot be charged until field wiring has been
completed.
Refrigerant may only be charged after performing the leak
test and the vacuum pumping.
When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in view of
the danger of liquid hammer.
Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when
charging refrigerant.
Ventilate the air if there was any refrigerant leakage
during the installation.
Leaked refrigerant will generate poisonous gas if
meeting fire.
Make sure there is no refrigerant leakage after the
installation.
Leaked refrigerant will generate poisonous gas if
meeting fire.
Allowed Lenght and Drop of Pipes
Requirements are different when installing the outdoor unit,
please refer to outdoor unit installation manual for detailed
information.
Material and Size of the Pipes
Three length(3m,5m,10m)of pipes are available to purchase.
8.2. Refrigerant pipe installation
NOTE
Drainage test Drainage test
Check whether the drainpipe is unhindered.
New built house should have this test done before paving
the ceiling.
Remove the test cover, and stow water of about 2000ml to the
water receiver through the stow tube.
Turn on the power, and operate the air conditioner under the
"COOLING" mode. Listen to the sound of the drain pump.
Check whether the water is discharger well (a lag of 1min is
allowed before discharging, according to the length of the drain
pipe), and check whether water leaks from the joints.
1
2
Stop the air conditioner, turn off the power, and reset the test
cover to its original position.
3
The drain plug is used to empty the water-receiver for
maintenance of the air conditioner. Please stuff it imposition at
all times during operation to avoid leakage.
The body's pump pipe and the drainpipe (especially the
indoor part) should be covered evenly with the out-let pipe
sheath (fittings) and be bound tightly with the constrictor to
prevent condensation caused by entered air.
To prevent water from flowing backwards into the air
conditioner while the air conditioner stops, please lean the
drainpipe down toward outdoor (outlet-side) at a degree of
over 1/ 50. And please avoid any bulge or water deposit.
Do not drag the drainpipe violently when connecting to
prevent the body from being pulled. Meanwhile, one
supportpoint should be set every 1~1.5m to prevent the
drainpipe from yielding.Or you can tie the drainpipe with the
connecting pipe to fix it.
In the case of prolonged drainpipe, you had better tighten its
indoor part with a protection tube to prevent it from loosing.
If the outlet of the drainpipe is higher than the body's pump
joint, the pipe should be arranged as vertically as possible.
And the lift distance must be less than 200mm, otherwise the
water will overflow when the air conditioner stops.
The end of the drainpipe should be over 50mm higher than
the ground or the bottom of the drainage chute, and do not
immerse it in water. If you discharge the water directly into
sewage, be sure to make a U-form aquaseal by bending the
pipe up to prevent the smelly gas entering the house through
the drain pipe.
9. CONNECT THE DRAIN PIPE
Install the drainpipe of the indoor unit
You can use a polyethylene tube as the drainpipe
(out-dia.37-39mm, in-dia.32mm). It could be bought at local
market or from your dealer.
Set the mouth of the drainpipe onto the root of the body's
pump-pipe, and clip the drainpipe and the out-let pipe sheath
(fittings) together firmly with the out-let pipe clasp (fitting).
The outdoor unit is factory charged with refrigerant. Some
systems require additional charging of refrigerant depending
on pipe lengths. The additional refrigerant to be charged
can be calculated from the following formule:
The standard pipe length is vary according to the requirements of
different area. For example, in North America area, the standard
pipe length is 7.5m(25ft). While in the other areas, the standard pipe
length is 5m(16ft).
Fixed-frequency R22 (orifice in the indoor unit):
Liquid side:φ6.35(1/4") (Total pipe length - standard pipe length)x30g(0.32oZ)/m(ft)
Liquid side:φ9.52(3/8") (Total pipe length - standard pipe length)x65g(0.69oZ)/m(ft)
Liquid side:φ12.7(1/2") (Total pipe length - standard pipe length)x115g(1.23oZ)/m(ft)
Fixed-frequency R22 (orifice in the outdoor unit):
Liquid side:φ6.35(1/4") (Total pipe length - standard pipe length)x15g(0.16oZ)/m(ft)
Liquid side:φ9.52(3/8") (Total pipe length - standard pipe length)x30(0.32oZ)/m(ft)
Liquid side:φ12.7(1/2") (Total pipe length - standard pipe length)x60g(0.64oZ)/m(ft)
Fixed-frequency R410A:
Liquid side:φ6.35(1/4") (Total pipe length - standard pipe length)x20g(0.21oZ)/m(ft)
Liquid side:φ9.52(3/8") (Total pipe length - standard pipe length)x40g(0.42oZ)/m(ft)
Liquid side:φ12.7(1/2") (Total pipe length - standard pipe length)x60g(0.64oZ)/m(ft)
Inverter R410A:
Liquid side:φ6.35(1/4") (Total pipe length - standard pipe length)x15g(0.16oZ)/m(ft)
Liquid side:φ9.52(3/8") (Total pipe length - standard pipe length)x30g(0.32oZ)/m(ft)
16
installation manual
17

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Midea MCDD-Serie wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Midea MCDD-Serie

Midea MCDD-Serie Bedienungsanleitung - Deutsch - 10 seiten

Midea MCDD-Serie Bedienungsanleitung - Englisch - 10 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info