Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.2 Acquisition of actual values
3.2.1 General remarks about faults in the measuring circuits
In the event of a faulty temperature sensor, the RVP201/211 always attempts to main-
tain the required comfort level in the best possible way, even if a certain amount of heat
is wasted.
In the case of serious faults that do not allow the RVP201/211 to ensure control, a fault
message will be generated. This is indicated on the controller front by the LED which
starts flashing when the current operating mode is overridden.
3.2.2 Flow or boiler temperature
Suitable are all temperature sensors that use a sensing element LG-Ni 1000 at 0 °C:
Clamp-on temperature sensor QAD22
Immersion temperature sensor QAE212…
Immersion temperature sensor QAP21.3 (complete with a ready connected cable)
If a fault occurs in the control sensor’s measuring circuit (short-circuit or interruption), the
control switches itself off (mixing valve closes or burner off, heating circuit pump on).
In any case, a fault message will be delivered; the LED on the controller front flashes.
3.2.3 Outside temperature
The following types of outside sensors can be used:
QAC22 with a sensing element LG-Ni 1000 at 0°C
QAC32 with a sensing element NTC 575 at 20°C
The controller automatically identifies the type of sensor connected.
If a fault occurs in the outside sensor’s measuring circuit, the control responds as fol-
lows:
Plants with a room temperature sensor:
The controller switches to pure room temperature control
Plants without a room temperature sensor:
The controller ensures control based on a fix outside temperature of 0 °C
A fault message is generated only when there is no actual value of the room tempera-
ture available. This is the case when no room unit is present or when the room tem-
perature measuring circuit is faulty. The LED on the controller front flashes.
3.2.4 Room temperature
The room temperature is acquired via a PPS (point-to-point interface). Only room units
that deliver suitable output signals can be connected to it.
The following types of room units can be used:
Room unit QAW50
Room unit QAW70 (room temperature sensor QAW44 can be connected in parallel)
It is also possible to connect an external switch for changeover of the current operating
mode to the PPS interface (also refer to "4 Handling"). When the switch is closed, the
room temperature cannot be measured.
Short-circuits or interruptions at the terminals do not trigger fault messages since these
statuses have a defined meaning:
Interruption = no room unit connected
Short-circuit = an external switch, if present, is activated
Types of sensors
Handling of faults
Types of sensors
Handling of faults
Types of sensors
Handling of faults
13

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP201 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP201

Siemens RVP201 Installationsanweisung - Deutsch, Englisch, Holländisch, Dänisch, Französisch, Italienisch, Spanisch, Schwedisch, Finnisch - 26 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info