Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.2.5 D.h.w. temperature
The d.h.w. temperature can be acquired with either a sensor or thermostat. For details
on the use of a thermostat, refer to "3.7 D.h.w. heating".
Suitable are all temperature sensors with a sensing element LG-Ni 1000 at 0 °C:
Immersion temperature sensor QAE212…
Immersion temperature sensor QAP21.3 (complete with a ready connected cable)
It is not possible to configure whether a sensor or a thermostat is connected. For this
reason, a short-circuit or interruption are permitted statuses so that no fault message
can be generated.
3.3 Flow or boiler temperature control
3.3.1 Setpoint adjustments
The following manual adjustments are made on the controller:
Setpoint for the normal temperature. The mid-position of the setting knob's scale
corresponds to a setpoint of 20 °C. Readjustments can be made within a range of ±
8 °C, giving a total setting range of 12…28 °C.
Setback for the reduced temperature. The setting knob's scale represents the set-
point for the normal temperature. The setback is adjustable within a range of
0…–12 °C.
The setpoints of the normal and the reduced temperature are entered directly in °C
room temperature. They are independent of whether or not the control uses a room
temperature sensor.
The lowest valid room temperature setpoint always represents the minimum setpoint for
the frost protection for the plant, even if a lower value has been set as the setpoint for
the reduced temperature. The setpoint for the frost protection for the plant is 5 °C (fixed
value).
3.3.2 Heating program
The controller has a plug-in type time switch for entering a 24-hour or weekly heating
program. For each heating period that uses the normal temperature, the start and end
of the period need to be set. Outside of the selected heating periods, the reduced tem-
perature
or protection temperature will be maintained.
With each type of time switch, several heating phases per day can be set.
In the automatic modes without using a time switch, the lower temperature (reduced or
frost protection) will be maintained.
The room unit QAW70 is used to override the heating program. For details, also refer to
"6 Mechanical design".
3.3.3 Compensating variables
The RVP201/211 differentiates between three types of outside temperatures:
The actual outside temperature (T
A
)
The attenuated outside temperature (T
AD
). It is generated by filtering the actual out-
side temperature by the building time constant. This means that compared to the ac-
tual outside temperature, the attenuated outside temperature is significantly damp-
ened, thereby representing the long-term development of the outside temperature.
The building time constant is a measure of the type of building structure and indi-
Types of sensors
Handling of faults
Outside temperature
14

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP201 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP201

Siemens RVP201 Installationsanweisung - Deutsch, Englisch, Holländisch, Dänisch, Französisch, Italienisch, Spanisch, Schwedisch, Finnisch - 26 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info