15.0 Dimmable loads
Load type Dimmable Load type / Dimming type Comment
Halogen lights and incandescent lamps for 230 V~ YES Reverse phase control –
Low-voltage halogen lights with electronic transformer YES Reverse phase control
*
Low-voltage halogen lights with laminated core transformer YES Phase control *
(toroidal core transformers and transformers from
Block and ABB except for type series... Lv) are unsuitable
Combined operation of low-volt halogen lights with YES Reverse phase control
*
Electronic transformer and 230 V~ incandescent lamps
Toroidal transformers NO X –
Metal halide lamps NO X –
Energy saving lamps NO X –
Fluorescent lamps NO X –
Lamps with own dimmer NO X –
Lamps with other electronic ballasts NO X –
* Only use transformers (Tronic transformers) that are suitable or approved and are operated at the minimum load.
Theben AG
Hohenbergstr. 32
D-72401 Haigerloch
Phone +49 (0) 74 74/6 92-0
Fax: +49 (0) 74 74/6 92-150
Service
Phone +49 (0) 90 01 84 32 36
Fax: +49 (0) 74 74/6 92-207
hotline@theben.de
Addresses, telephone numbers etc. at
www.theben.de
Please note!
The 3 stars on the top of the LUXOR 405 denote
a 3rd generation device.
This means that only these devices with LUXOR
411 (sensor module) and LUXOR 414 (timer
module) can be controlled.
16.0 Positive list of conventional transformers
tested
Type Supplier / Power [W]
Manufacturer
mind max
LDT 60 Bürklin 45 60
LTV 250/96 TB Reichelt 180 250
LTV 300/96 Reichelt 200 300
Type 120/500 Reichelt 300 500
(LTV 500/135)
Si-TR 300-230/12 Lv ABB 250* 300
* Not stated, therefore please use 80 % of maximum value.