Inst: System parameters: Input, “C_b
In case of mutizone regulation “WFHC Master RF with or without Heat&Cool function” is installed you
could use the input 1 to connect the pump relay output to swtich off the circulation pump1 in case of no
water circulation demand is asked in the house.
Note:
-
The heating output will follow the circulation demand from the pump1.
2)
Input2
Inst: System parameters: Input, “HC
You could use the input 2 to connect the an external signal which give the Heating or Coling working mode
of the installation (This signal could be done directly by a reversible input).
“HC” is only available if Input1 is set on “no or Aqua”
Inst: System parameters: Input, “Aqu
You could use the input 2 to connect the an immersion thermostat witch schould be placed in a storage
tank. In Heating mode this immersion thermostat will be use to switch off the circulation pump to avoid cold
water circulation in the circuit if the storage tank is discharged.
The immersion thermostat connected on the Input2 will manage the working of the main circula-
tion pump (Mixed circuit) if the ClimaticControl-HC drive only one pump.
In the installation with two circulations pumps, the immersion thermostat connected on the Input2
will manage the working of the 2nd circulation pump (direct circuit).
Note:
-
The heating output will stay activated even if the aquastat have stopped the circulation pump.
-
To avoid problem in cooling mode, if the storage tank is filled with cold water (by heat pump...) the
aquastat function will be automatically desactivated.
Inst: System parameters: Input, “C_b
In case of mutizone regulation “WFHC Master RF with Heat&Cool function” is installed you could use the
input 2 to connect the pump relay output to swtich off the circulation pump in case of no circulation demand
is asked in the house.
The WFHC connecting box connected on the Input2 will manage the working of the main circula-
tion pump (Mixed circuit) if the ClimaticControl-HC drive only one pump.
In the installation with two circulations pumps, the WFHC connecting box connected on the Input2
will manage the working of the 2nd circulation pump (direct circuit).
Example 1: Reversible installation with circulation pump (UFH application).
In1 Used to change the working mode of the installation, signal from Heat Pump (Inst: System parameters: Input, “HC”)
In2 used to stop the pump when D.H.W is in demand (Inst: System parameters: Input, “Aqu”)
Closed =
Cooling
Mode
Attention:
In case of the CLIMATICCONTROL-HC must be linked with the Heat pump (from the Heat /
Cool switch)
Pay attention to check the compatibility of the electrical signal before connection.
The inputs 1 or 2 (Inst: Parameter menu: In1, In2 “HC”) need a live signal “Phase L” to works
in cooling mode.
Fig. 10
> T °C
Immersion
thermostat
Heating &
Cooling signal
L
L’
2
1
C
In1 In2
4 2
12

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Watts Climatic Control Heating and Cooling wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info