Operation and maintenance manual - EN
• Parameter S38 – deactivation difference for parameter S37, of the pump in the boiler circuit
(S14 = 13 or S6 = 13)… (2 K)
If the temperature of the boiler TK drops by more than the deactivation difference S38, the pump
in the boiler circuit will be turned off in the OPERATION or STOP (burn-out) modes.
• Parameter S39 – characterizes the emergency temperature of the boiler TK, during which the
pump in the boiler circuit will be activated (S14 = 13 with modules AD02 or AD03)… (93 °C)
Activation will be carried out regardless of special functions of the burner (function S40). The
function works based on the deactivation difference specified in parameter S38.
• Parameter S40 – is the function for after-running of the pump in the boiler circuit used based on
boiler type (S14 = 13, S6 = 13)… (0)
a) S40 = 0…. The automatic deactivation function for the pump in the the boiler circuit after the
pellet burner burns out is off (after the time specified in parameter T5 runs out). The pump will
be switched off after the temperature of the boiler TK drops (S38, S39). Designated for ceramic
boilers with a large momentum (with the option of stoking with wood).
b) S40 = 1... The automatic deactivation function for the pump in the boiler circuit after the pellet
burner burns out is on. The pump will be switched off immediately after the burner burns out, after
the time specified in parameter T5 runs out. The function designated by parameter S39 is active.
Designated for boilers with minimal momentum without ceramics (D14P, P14, D21P, P21, D25P, P25).
• Parameter S41 – is the function for automatic burner cleaning with compressed air after a specific
number of working cycles (burn-out). The function assumes use of both reserve outputs (S6 = 16,
S14 = 15 (S67 = 15, S68 = 16 in case of AC07X-C module)) – non-standard function (4)
a) S41 = 1 - 9… function when the cleaning of the burner will be performed only once after ru-
nning a given number of cycles (1, 2, 3, 4, 5, 6, 7, 8, 9 - number of cycles)
b) S41 = 11 - 19… function when the cleaning of the burner will be performed always twice after
running a given number of cycles (11 = 1, 12 = 2, 13 = 3, 14 = 4, 15 = 5, 16 = 6, 17 = 7, 18 = 8,
19 = 9 - number of cycles) (from 1.4.2013)
If the parameter S41 = 0 or 10, the function is turned off.
• Parameter S42 – is the function for automatic burner cleaning with compressed air after a specific
period of operation time has passed (in one cycle). Once the subsequent working cycle has ended
(burn-out), the burner tubing is cleaned. The function assumes use of both reserve outputs (S6 = 16,
S14 = 15 (S67 = 15, S68 = 16 in case of AC07X-C module)) – non-standard function… (6 hours)
The value set is the actual time in hours.
• Parameter S43 – is the function for automatic burner cleaning with compressed air after a specific
period of operation time has passed. Once the set time has bassed, the burner immediately burns
out (AUTOSTOP), it is cleaned and once again run. If required at all requirements for START are
met. (regardless of S41 and S42 parameters). The function assumes use of both reserve outputs
(S6 = 16, S14 = 15 (S67 = 15, S68 = 16 in case of AC07X-C module)) – non-standard function…
(12 hours)
This is the sum of operating hours of all completed cycles.
The value set is the actual time in hours.
64

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Atmos A25 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Atmos A25

Atmos A25 Bedienungsanleitung - Deutsch - 70 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info