Operation and Maintenance Manual - EN
• Parameter S42 – is the function for automatic burner cleaning with compressed air after a specific
period of operation time has passed (in one cycle). Once the subsequent working cycle has ended
(burn-out), the burner tubing is cleaned. The function assumes use of both reserve outputs (S6 = 16,
S14 = 15 (S67 = 15, S68 = 16 in case of AC07X-C module)) – non-standard function… (6 hours)
The value set is the actual time in hours.
• Parameter S43 – is the function for automatic burner cleaning with compressed air after a specific
period of operation time has passed. Once the set time has bassed, the burner immediately burns
out (AUTOSTOP), it is cleaned and once again run. If required at all requirements for START are
met. (regardless of S41 and S42 parameters). The function assumes use of both reserve outputs
(S6 = 16, S14 = 15 (S67 = 15, S68 = 16 in case of AC07X-C module)) – non-standard function…
(12 hours)
This is the sum of operating hours of all completed cycles.
The value set is the actual time in hours.
• Parameter S44 – is the compressor function for automatic cleaning of the burner by compressed
air, which determines the duration of compressor operation used for preparing a sufficient amount
of compressed air (pressure function S6 = 16) - nonstandard function… (2 min )
The set value represents the actual time in minutes.
• Parameter S45 – is the electric valve function for automatic cleaning of the burner by compressed
air, which determines how long the el. valve is open to perfectly clean the combustion chamber of
the burner (S14 = 15) - nonstandard function… (2 s)
The set value represents the actual time in seconds.
• Parameter S46 – is the burner fan function which sets the type of used fan with rotation scanning.
Number of impulses.… (
12-EBM
)
• Parameter S47 – is the function of fan 2 which sets the type of used fan with rotation scanning.
Number of impulses – do not change the factory setting(0)
a) S47 = 12 - EBM..... radial blower of the burner
b) S47 = 4 - ATAS..... exhaust blower of the boiler
c) S47 = 0..... second method for switching off the blower 2 speed sensing
• Parameter S48 – characterizes temperature TEMPERATURE A in the applications of function
S6 = 17 to 36… (75 °C)
This is a free function for the reserve output R (R5) on the first position (Temperature A = first
position in function S6 = 17 to 36 (S67 = 17 to 36)).
• Parameter S49 – characterizes the activation or deactivation difference for TEMPERATURE A
in the applications of function S6 = 17 to 36… (5 K)
This is the difference for the free function of reserve output R (R5) on the first position (difference
for Temperature A = difference for the first position in the function S6 = 17 to 36 (S67 = 17 to 36)).
• Parameter S50 – characterizes TEMPERATURE B in the applications of function S6 = 25 to
36…(75 °C)
This is a free function for the reserve output R (R5) on the first position (Temperature b = second
position in function S6 = 25 to 36 (S67 = 17 to 36)).
46

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Atmos A45SPT wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info