TDMA CONTROL 601/701:
15
Published 07/2007
2.5.3 Return Flow Temperature Raising
Main Menu 12:34
Heating Input
Both the CONTROL 601 and the CONTROL 701 have a
programmable temperature difference regulating function
which can be used to control the hydraulic system’s return
flow temperature raising.
Return Flow Temp. Raising Difference:
2...24 K
The temperature difference by which the temperature of
the return flow temperature raising sensor of the thermal
store must be higher than that at the return flow sensor can
be set here. This activates the „Return Flow Temperature
Raising“ function (the switch over valve is switched to AB-
A). The hysteresis is set at 2K in the factory.
ADVICE:
Attention must also be paid to the „Back up heating via
CONTROL“ function on page 6 with the „Return flow
temperature raising“ function.
Temperature difference switch:
Input – Function – Output
Sensor description
Function
Return flow temperature
raising thermal store sen-
sor
(Art. N
o
. RE 046)
Return flow temperature rai-
sing
Return flow temperature
sensor
(Art. N
o
. RE 046)
Return flow temperature rais-
ing
Winter switch over
Output: Return flow temperature raising (Switch over valve)
2.6 Boiler Operating Functions (Boiler Input
Data)
Main Menu 12:34
Boiler Inputs
All settings for the boiler (e.g. oil or solid fuel) , the boiler
pump and the thermal store loading pump are entered
here.
2.6.1 Boiler (Oil, Gas, Pellets)
The hydraulic system switch controls the operation of either
the boiler pump or the thermal store loading pump. The
relationship is as follows:
Regulator setting
automatic switching to
Buffer logic
Boiler pump
Return flow tempera-
ture raising
Thermal store loading pump
No setting
Thermal store loading pump
Boiler Temperature
minimum : 0...70 °C
The minimum temperature at which the boiler or thermal
store loading functions are activated is set here.
Boiler temperature
maximum : 50...90 °C
The maximum boiler temperature at which the boiler
(burner) will be switched off via the zero voltage contact or
the 0 – 10V interface is set here.
Boiler difference
maximum: 0....60 K
Heating Operation: The temperature difference between
the calculated heating target temperature and the buffer
logic difference (when the Buffer logic function is activated)
and the actual boiler temperature is entered. When the
actual boiler temperature is higher than the target tem-
perature by this set temperature difference the burner will
switch off.
Hot Water Back up Heating Operation: The temperature
difference between the hot water target temperature and
the actual boiler temperature is set here. When the actual
boiler temperature is higher than the target temperature by
this set temperature difference the burner will switch off.
Example: Boiler heating
Heating circuit target temperature:
50 °C
Hot water back up heating target
temperature:
55 °C
Boiler Difference Maximum:
15 K
If during hot water back up heating operation the boiler
reaches a temperature of 70 °C, the boiler will switch
off. During heating operation the boiler will switch off at
65 °C. However, when the Buffer logic function is acti-
vated (e.g. Buffer logic difference : 6 K), the boiler will
switch off at 71 °C.
Boiler Input: Single stage / modulated op-
eration
This function enables single stage or modulated operation
of the boiler.
Single Stage Operation: The boiler is switched on and off
via the zero voltage contact.
Modulated Operation: The boiler is controlled via a volt-
age of between 0 to 10V. The voltage depends ofn the
temperature difference between the target and actual
boiler temperature.
The following 6 menu points are only to be found in the
professional menu for modulated boiler operation.
Minimum : 2...50 k W
Boiler Capacity
The minimum boiler capacity for modulated boiler regula-
tion is set here.
15

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Consolar Control 601 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info