TDMA CONTROL 601/701:
17
Published 07/2007
Solid Fuel Boiler Tempera-
ture Sensor
(Art. N
o
. RE 046)
Minimum temperature
Solid Fuel Boiler Differ-
ence
Thermal Store Tempera-
ture Sensor –Solid Fuel
Boiler
(Art. N
o
. RE 046)
Solid Fuel Boiler Differen-
ce
Output: Solid Fuel Boiler (Pump)
2.6.3 Buffer Logic
This function enables the boiler to be switched off when the
buffer region of the thermal store has reached the heating
target temperature, whether this has been achieved from
solar energy or by using the boiler.
The buffer logic controls the boiler operation in relation to
the external temperature. The additional „lower buffer
temperature sensor“ which is situated below the „upper
buffer temperature sensor“ enables the boiler to run longer
in order to load the buffer region between these two tem-
perature sensors.
Buffer Logic
Difference : 2...24 K
This function enables the temperature difference to be set
by which the temperature in the heating buffer region
(„lower buffer sensor“ and „upper buffer sensor “) must be
higher than the heating target temperature before the
„boiler on/off“ function is activated.
Buffer Logic
Hysteresis : 1...10 K
The switch hysteresis for the buffer logic can be set here.
Function: Buffer Logic
The Input activates the output de-
pendant on
Boiler on/off out-
put
„lower buffer sensor“ and „upper
buffer sensor“ temperature
heating circuit inflow target tem-
perature 1 plus Buffer logic differ-
ence minus Hysteresis
Boiler On („Boiler
= on/off“ contact
= closed)
Hot Water Back up Heating acti-
vated
Frost protection active
„lower buffer sensor“ and „upper
buffer sensor“ temperature
Heating circuit inflow target tem-
perature 1 plus Buffer Logic Dif-
ference
Boiler Off („Boiler
= on/off“ contact=
open)
Heat limits exceeded
Example: Buffer Logic
Heatin Circuit Target Temperature:
50 °C
Upper Buffer Sensor:
48 °C
Lower Buffer Sensor:
42 °C
Buffer Logic Difference:
8K
Buffer Logic Hysteresis:
5K
When the upper buffer sensor and lower buffer sensor
reach a temperature of 58
o
C the „boiler on/off“ contact
is opened and the boiler is switched off. When the lower
buffer sensor and upper buffer sensor record a tempera-
ture of below 53 °C, the „boiler on/off“ contact is
closed and the boiler is switched on.
2.7 T-PRO
Main Menu 12:34
T PRO Input
The CONTROL 601/701 regulators have all-purpose tem-
perature difference regulating capabilities which enable
control of hydraulic switches of different types.
Temperature Sensor 2
Yes / No
If the „Temperature Sensor 2: No“ option is set then the T-
PRO will function as one temperature switch.
T- P R O Difference:
0...30 K
This function is used to set the temperature difference by
which the temperature at Sensor 1 (source) must be higher
than the temperature at Sensor 2 (sink) so that the „T-PRO
function is activated.
T P R O H y s t e r e s i s:
0...30 K
To prevent the contact switching continually on and off, the
switch hysteresis is set here.
T e m p e r a t u r e
m i n: 0...100 °C
T e m p e r a t u r e
m a x : 0...140 °C
Minimum or maximum values can be set for both tempera-
ture sensors (T-PRO Sensor 1 and 2) here.
T-PRO Extended Running:
0...60 Min.
The „T-PRO“ function will only be deactivated once the
pre-set extended running time has expired.
Use the T - P R O Time Switch:
Yes / No
If the time switch option „Yes“ is set the T-PRO will only be
active during the two set time periods.
T - P R O :
Each Day/Every Day/Weekend-
Weekdays
The time switch is set as described in paragraph 2.4.1.
Example: Temperature Difference Regulator
Temperature sensor T2:
Yes
T-PRO difference:
4K
T-PRO hysteresis:
2K
17

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Consolar Control 601 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info