TDMA CONTROL 601/701:
19
Published 07/2007
code(3003) The input of system parameters should only be
carried out by trained personnel.
2.10 PC- Interface
The CONTROL 601/701 can be connected to a PC via a
serial interface. The solar thermal heating system can be
monitored and the settings made via the PC. „On-line Op-
eration“ allows records of temperature, yield and energy
to be made and for this information to be presented as
graphs and printed out. The data can be imported into an
MS-Excel database. Diagram 1 is a view of the PC-
software window.
„Off-line Operation“ allows the following data to be saved
and read out later:
Daily insolation
Daily maximum collector yield
Daily maximum collector temperature
Daily maximum upper thermal store temperature
Total insolation
The interface is installed by fitting the circuit board into the
module slot in the upper housing of the regulator. (see „In-
stallation“ on page 37 or page 58). The PC-Interface is
available as a package suitable for Window 95, 98 and
NT. For Windows version XP with USB connection a USB-
RS323 converter (e.g. Digitus DA-70119) is necessary.
3 Disruption and Function
Control
If a temperature sensor detects and reports a malfunction
(short circuit or interruption), the regulator will react ac-
cording to the relationships listed in the following tables.
Any disruption will cause the LCD indicator to flash and
the fault will be shown in the display panel. An interrup-
tion will be shown as:
Interruption in Sensor
N
o
. ...
And a short circuit as:
Short Circuit in Sensor
N
o
. ...
A disruption notice and a response to it will only occur for
a function which is activated. That is, if a function (e.g.
yield or frost protection) is not activated and no sensor is
connected, no disruption will be detected or notified, and
there will therefore be no response to a disruption in the
sensor.
3.1 Regulating the Solar Thermal System without
Extra Functions
Sensor Disruption:
Response
Collector Sensor
Solar pump = Off
Cooling = Normal operation
Hot Water Back up Heating = Normal Op-
eration
Upper Thermal Store Sensor
Solar pump = Off
Cooling = Off
Hot Water Back up Heating = Off
Lower Thermal Store Sensor
Solar pump = Off
Cooling = Normal operation
Hot Water Back up Heating = Normal opera-
tion
3.2 Regulating the Solar Thermal System with
Activated Frost Protection
Sensor Disruption
Response
Collector Sensor
Solar pump = Off
Cooling = Normal operation
Hot Water Back up Heating = Normal Opera-
tion
Upper Thermal Store Sen-
sor
Solar pump = Off
Cooling = Off
Hot Water Back up Heating = Off
Lower Thermal Store Sen-
sor
Solar pump = Off
Cooling = Normal operation
Hot Water Back up Heating = Normal Opera-
tion
Frost Protection Sensor
Solar pump = Normal operation and when the
collector temperature is < 20
o
C = On and if
the collector temperature > 22
o
C then Solar
pump = Off
Cooling = Normal operation
Hot Water Back up Heating = Off
Frost Protection Sensor
and Collector Sensor (short
circuit)
or
Frost Protection Sensor
and Collector Sensor (short
circuit) and Lower Thermal
Store Sensor
Solar pump = On and
If the upper thermal store temperature is >
90°C,
then solar pump = Off
Cooling = Normal operation
Hot Water Back up Heating = Off
19

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Consolar Control 601 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info