Installation manual: Oasis security system JA-80K - 5 - MKE51801
Communicator connector – allows the connection of an
optional communicator to the main board.
Internal wiring connector – connects the internal wiring in the
control panel housing.
Terminals:
AC 20V the transformer output is connected here.
01, GND, 02 are hard-wired inputs for the control panel.
The reactions to triggering these inputs are determined by the
settings of addresses 01 and 02. The factory-set natural
reaction for these hard-wired inputs is a delayed alarm in
section C.
Terminals 01 and 02 use resistors in connected double
balanced loops to sense loop stand-by, activation or
tampering as follows:
o Connected to GND via a 1 kΩ resistor = untriggered input
o Connected to GND via 2 to 6 kΩ = triggered input,
o Connected to GND via less then 700Ω or more then 6 kΩ
= tamper signal
o Stand-by (untriggered) input zone must have 1 kΩ
o Up to five normally-closed door/window contacts can be
connected in series to enable one hard-wired input to be
used for multiple contacts with each contact having a 1kΩ
resistor in parallel (see the diagram below).
o Multiple normally-closed tamper contacts should be
connected in series without any parallel resistors. The
number of tamper contacts is unlimited and can be
combined with trigger contacts having parallel resistors (see
the diagram below).
o For wiring examples, see the below diagram.
o If you enroll a wireless device to address 01 or 02, the
corresponding input terminal will be disabled.
o If you do not use an input terminal and you do not enroll a
wireless device to its address, then the terminal must be
connected to the GND terminal via a 1 kΩ resistor.
NC normally closed contact for the external warning relay.
NO - normally open contact for the external warning relay.
EWC – common contact for the external warning relay max.
relay contact rating: 1A/60V. The control panel also transmits
the external warning relay signal via radio for wireless sirens.
IW – internal warning (siren) output. This output is grounded
during an internal alarm. A standard siren can be wired between
terminals +U and IW (max. 0.5A).
The IW output status is also
transmitted by radio for the IW siren.
The main difference between internal and external warning is during
the entrance delay period. If any instant detectors are triggered during
the entrance delay period, e.g. a child running straight to the living
room, only an internal warning will be triggered and an external
warning will only follow if the entrance delay has been exceeded.
PGX, PGY – are a pair of terminals providing programmable
outputs. If an output is activated it switches to GND with a
maximum load of 0.1A/12V. The factory-default setting of PGX is
the function ON/OFF which can be operated from the keypad by
the instruction 81 / 80 or using keys
). The factory-default
function of PGY is that it will be activated if any section of the
system is set. The status of PG outputs is also transmitted by
radio for AC and UC output modules.
GND – common ground connection
A,B – digital bus data
+U – back-up power supply (10 to 14V), 1A fuse. Max.
continuous load 0.4 A (max. intermittent load 1 A, for 15
minutes, once an hour). If the 1A fuse is blown, the control panel
will indicate power supply fault.
5. Wired keypad connection
GND A B U+
IN
+U
B
A
GND
GND
control and programming
keypad JA-80E
modular connection
cable
The control panel can be operated and programmed by JA-
80F wireless keypads and/or a JA-80E hard-wired keypad. A
hard-wired keypad can be connected to the control panel either
by flat telephone cable (max. length 10 metres) using RJ
connectors, or via twisted-pair cable (max. length 100 metres)
connected to the digital bus terminals (GND, A, B, +U).
We recommend only having a single JA-80E hard-wired
keypad in the system.
6. Back-up battery
It is possible to use a Jablotron-brand 12V back-up battery in
the control panel with capacities of 1.3Ah or 2.6no Ah. The
capacity to use depends on the total power consumption of the
system and the desired back-up period.
Euro-standard EN 50131-1 specifies a 12 hour minimum back-
up time for grade 2 systems. The standby consumption of all
system devices is shown in table 1.
Table 1- standby consumption of system devices
With a 1.3Ah back-up battery 12 hours of back-up time can be realised if
current consumption does not exceed 85mA. With 2.2Ah batteries
150mA should not be exceeded to achieve the same. This only takes
80% of the battery capacity into account as 20% has to be reserved for
battery aging effects.
The average back-up battery lifetime is up to 5 years after which it must
be replaced. The back-up battery is automatically charged and its
condition is monitored by the system. If the system is being run on only
the back-up battery a technical alarm occurs when the battery is
nearly discharged. If the voltage gets too low the battery will be
Device mA Note
Control panel JA-80K 50 No communicator
Keypad JA-80E 30
Keypad JA-80H (N) 60 Including a WJ-80 interface
Communicator JA-80Y 35
Communicator JA-80V 30
Wireless devices are not powered from the control panel.
5

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Jablotron JA-80K wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Jablotron JA-80K

Jablotron JA-80K Bedienungsanleitung - Englisch - 1 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info