In the event that alarm A05 is triggered often, please note that:
A05
Safety devices alarm
Smoke pressure switch intervention Check for chimney obstructions / door open
Fuel loading hatch Close the hatch.
Lower the fuel level in the hopper.
Open stove door Close the door
you must check some points to verify the cause of the problem and possibly act on some adjustments and/or safety devices to restore the
correct operation of the product.
However please note that all the adjustments and alterations aecting the operational safety devices, must only be performed if THE
PRODUCT IS INSTALLED IN COMPLIANCE WITH THE STANDARDS AND LAWS IN FORCE AND IF IT IS SERVICED PROPERLY BY AUTHORISED AND
SPECIALISED PERSONNEL. Alterations performed randomly, to ensure operation of the product even in the non-compliant conditions, can
cause serious damage to property and injuries to people.
Attention!
The adjustments must only be carried out by authorised and qualied personnel under their responsibility and
by checking the conformity of the installation beforehand. The manufacturer declines all liability for damage to
property or injuries to people in the event of altering the safety devices.
All liability for improper use of the product is entirely borne by the user and relieves the Manufacturer from any civil
and criminal liability.
Series of stoves equipped with a pressure switch installed on the hopper with the sampling point positioned on the bottom, to the right of
the gear motor. This system protects the whole system ensuring tightness of the stove throughout its duration.
It is important to understand that the pressure switch can intervene with each signicant drop in negative pressure and may be due to:
• The ue clogging.
• The presence of a foreign body in the ue (birds, nests, clogged grates, etc.).
• Wind coming through the ue because it is unprotected or the installation was wall-mounted or required no ue.
• Cold air draught down the ue.
• A damaged pressure switch.
• Blocked membrane inside the pressure switch because soot or pellet dust ltrated.
• The pellet hopper is open or ajar for more than 60 seconds (60 seconds is the estimated time to reload the hopper).
• Pellet trapped between the hopper cover and the hopper, which prevents the gasket to seal.
• Broken/worn hopper cover gasket.
• The gasket between the feed screw and the boiler is damaged or positioned incorrectly.
• Fire door is open or the gasket is worn.
• Clogged lateral smoke exchangers.
• Inspection caps with gaskets installed incorrectly after maintenance.
• Feed screw clogged by a compressed pellet at the top.
• The installation is compliant and the ue/smoke tting does not generate obvious obstructions which can stop the release of smoke,
such as: long horizontal sections (over 3 metres), uninsulated smoke ducts, “wall-mounted” smoke exhaust without proper terminals
(installation regulated and permitted in France only [ZONE 3])
• Internal air extraction or recirculation systems (e.g. VMC systems) that generate internal negative pressure exceeding those required
by law (not exceeding 4 Pa)
• Installed without combustion air ducting, it is crucial to check that there is an ecient air inlet dedicated to the stove, according to
the specications referred to in chapter 2 of this manual.
The electronic board has also been equipped with an automatic device with a timer and contactors which increases the RPM of the smoke
extractor so as to restore the negative pressure inside the hopper and therefore the pressure switch, if the cover is opened for top-up or if
there is an immediate or occasional pressure drop such as gusts of wind outside. If the pressure drop lasts for more than 60 seconds, the
product is set in an alarm statue (A05 or A18)