CA-6 SATEL 7
panel outputs, it activates the fire alarm verification function. The verification operates as
follows: the first violation cuts the fire detectors power supply off for about 15 seconds.
The power-down results in reset of the violated detectors. Then, the power supply is
restored, but the panel will not control the “24H fire” zones for ten to twenty seconds
because of the balancing of detectors. Next, the control panel enters the special mode of
fire detectors control, which lasts about 90 seconds. If a repeated detector violation occurs
during that time, a FIRE alarm will be triggered. Otherwise, the control panel will go over
to the normal control of “24H fire” zones (duration of the whole verification process is
approx. 2 min.). The output reacts to the "RESET power supply" function (user function 9).
29 power supply with RESET function the output is designated to power detectors which
require a periodical power cut-off until the state memory is cleared. The RESET function is
activated from keypad through the user function 9 (calling: [CODE][
*
][9]). The voltage is
cut off for time programmed as the output active time.
30 TIMER the output is controlled by the control panel clock; it is activated/deactivated in the
hours indicated by a corresponding TIMER (see: Functions programming TIMERS).
31 audible alarm status the output signals the audible armed mode. Operation of the output
can be limited to the selected "list of zones" or partition.
32 full arm status the output is only active when all zones/partitions assigned to it are in the
armed mode.
33 ARM/DISARM/CLEAR ALARM the output signals the particular system states with,
respectively, one, two, or four pulses 0.16 s each.
34 alarm in keypad silent alarm signaling in the partition keypad.
35 power supply on armed mode it functions similarly to the ARM STATUS output, but it is
activated right after "exit delay" starts, not after changeover from the exit delay to the
armed mode (it can be used, for example, as indicator or power supply output for
microwave detectors in spaces where people stay).
36 signalling: LED – the output can control a LED to indicate the following statuses:
- off – control panel disarmed
- steady light – control panel armed
- blinking light – the control panel armed, there was alarm or trouble
Note: If in the armed mode any zones are violated in the system, the LED will be
blinking and will only change to steady light after the violation ends.
37 signalling: relay the output can control a relay. The output becomes active after arming,
and inactive after an alarm is triggered, a trouble occurs, or the system is disarmed.
Note: If in the armed mode any zones are violated in the system, the output will
become active after the violation ends.
38 not used (do not program).
39 no guard code the output is activated by a timer programmed as the partition control
TIMER, unless a guard code is entered within the timer specified time.
40 service mode status the output is activated if the control panel service mode has been
called from any keypad.
41 battery low status – the output, which state is updated after each battery voltage test.
Partitions
A new partition is created when at least one zone is assigned to it. The CA-6 permits creating
of two partitions to which any outputs, telephone numbers and pager messages can be
assigned, and thus enables two alarm systems to be built on the basis of one CA-6 control
panel. The partitions can be controlled from a keypad (access codes assigned to the
partitions) as well as by means of control zones. Both partitions can be controlled at the
same time.
Because the sirens connected to the outputs can be activated by selected zones, the
assignment of zones to partitions will define which codes can clear alarm on particular sirens.
9

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Satel CA-6 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Satel CA-6

Satel CA-6 Zusatzinformation - Deutsch - 19 seiten

Satel CA-6 Bedienungsanleitung - Deutsch - 19 seiten

Satel CA-6 Installationsanweisung - Deutsch - 80 seiten

Satel CA-6 Bedienungsanleitung - Deutsch - 18 seiten

Satel CA-6 Zusatzinformation - Englisch - 40 seiten

Satel CA-6 Kurzanleitung - Englisch - 8 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info